Product Specifications; Specifications - Mitsubishi Electric PWFY-P100VM-E-BU Data Book

Hide thumbs Also See for PWFY-P100VM-E-BU:
Table of Contents

Advertisement

Product Specifications
II

1. Specifications

(1) PWFY-P100VM-E-BU
Model
Power source
Heating capacity
(Nominal )
Power input
Current input
Temp. range of
for outdoor unit
heating
for heat source unit
for PWFY
Connectable
Total capacity
outdoor unit
Model / Quantity
/heat source unit
Sound pressure level (measured in anechoic room)
Diameter of
Liquid
refrigerant pipe
Gas
Diameter of
Inlet
water pipe
Outlet
Field drain pipe size
External finish
External dimension H × W × D
Net weight
Compressor
Type
Maker
Starting method
Motor output
Lubricant
Circulating water
Operation volume
Range
Protection on Internal circuit
High pressure protection
(R134a)
Inverter circuit (COMP)
Compressor
Refrigerant
Type × original charge
Control
Design pressure
R410a
R134a
Water
Drawing
External
Wiring
Standard attachment
Document
Accessory
Optional parts
Remark
Note:
*1 Nominal heating conditions (PWFY conditions are indicated in the parentheses.)
<R2-series>
Outdoor temp. : 7°CDB/6°CWB (45°FDB / 43°FWB)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0 m (0 ft)
(Inlet water temp. 65°C
* Due to continuing improvement, the above specifications may be subject to change without notice.
* The unit is not designed for outside installations.
* Please do not use the steel material for the water piping material.
* Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less.
* Please always make water circulate or pull out the circulation water completely when not using it.
* Please do not use ground water and well water.
*1
kW
*1
kcal / h
*1
BTU / h
kW
A
W.B
-
-
dB<A>
mm(in.)
mm(in.)
mm(in.)
mm(in.)
mm(in.)
mm
in.
kg(lbs)
kW
m
/h
3
MPa
MPa
MPa
<WR2-series>
Circulating water temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0 m (0 ft)
Water flow rate 2.15 m
/h)
(Inlet water temp. for PWFY side 65°C
3
1-phase 220-230-240V 50/60Hz
-20~32°C (-4~90°F) R2-series
10~45°C (50~113°F) WR2-series
50~100% of outdoor unit/heat source unit capacity
PURY-(E)P
800 (785 without legs) × 450 × 300
31-1/2" (30-15/16" without legs) × 17-3/4" × 11-13/16"
Inverter rotary hermetic compressor
MITSUBISHI ELECTRIC CORPORATION
High pressure sensor, High pressure switch at 3.60 MPa (601 psi)
Over-heat protection, Over-current protection
Discharge thermo protection, Over-current protection
R134a × 1.1kg (0.50lbs)
Installation Manual, Instruction Book
Strainer, Heat insulation material, wire
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
Water flow rate 2.15 m
* Install the outdoor unit (R2-series) in an
environment where the wet bulb temp. will
not exceed 32°C.
* The water circuit must use the closed circuit.
* Please do not use it as a drinking water.
- 3 -
PWFY-P100VM-E-BU
12.5
10,800
42,700
2.48
11.63 - 11.12 - 10.66
10~70°C (50~158°F)
Y(S)LM-A(1)(-BS)
PQRY-P
Y(S)HM-A
44
ø9.52 (ø3/8") Brazed
ø15.88 (ø5/8") Brazed
PT3/4 Screw
PT3/4 Screw
ø32 (1-1/4'')
NO
59 (131)
Inverter
1.0
NEO22
0.6~2.15
LEV
4.15
3.60
1.00
WKB94L762
WKE94C229
NONE
Unit converter
kcal/h = kW × 860
BTU/h = kW × 3,412
cfm
= m
/min x 35.31
3
lbs
= kg / 0.4536
/h)
3
* The specification data is subject