[2.1 Selection of Installation Place]
1. Select a suitable staging area in which to assemble the unit. With the customer's approval, determine the best
placement of the assembled unit. Choose a safe, sequestered area where the inquisitive can't reach it, and keep it
out the way of any direct air discharge.
[2.2 Prior to Installation]
1. This packing contains the following parts.
[A] Wired Controller (Qty.: 1, For Operation Control)
[B] Screw <M4x16L> (Qty.: 2, For securing the mounting bracket to the wall.)
[C] Ring Core (Qty.: 1)
[D] Band (Qty.: 1, For Fixing Cable to Ring Core)
[E] Operation Manual (Qty.: 1)
[2.3 Installation Procedures]
1. Insert the edge of the slotted screwdriver into the groove at the bottom of the holding bracket, push and turn the
slotted screw driver to separate and remove the controller from the holding bracket.
Groove Part
2. Attach the controller to the holding bracket and connect the cable as follows.
A. In Case of Exposing the Controller Cable
Secure the holding bracket
onto the wall with
screws (accessory).
P5417086
Slotted
Screw Driver
Figure Seen from Bottom Side
Cable
Band Stopper
(Field-Supplied)
Approx. 6mm
Trace-out Hole
Attach the stopper (plastic band)
to the cable at the inside of
the draw-out hole.
Feed the cable with its
sheath peeled through
the groove.
Peel away the insulation
at the end of the cable
and clamp the M3 (field-
supplied) solderless
terminals .