Wire and Terminal Specifications
Terminal/Connector
D1 power input
line/neutral/ground
D1 HOand D2 power input
line/neutral
D4 maintained power input
line/neutral
D4 emergency drivers
sense power input
line/neutral/ground
Power Input
ground
DMX In/Thru
RJ45 Connectors
Outputs for all D1, D2, and
D4 Series Drivers with Molex
connectors
Outputs for D4 drivers with
terminals
Note:
and D2 Series drivers is 15 m (49 ft).
Maximum supported wire length between any load and a D4 Series driver is 10 m
(33 ft).
16
Conduit
Entry
½ in
Up to 6 mm
conduit
stranded
½ in
0.5–10 mm
conduit
½ in
0.2–2.5 mm
conduit
½ in
2.5–10 mm
conduit
Cat5e (or better) minimum 0.2 mm
½ in
(24 AWG) conductors terminated to
conduit
T568B standard
½ in
Follow Class 2 wiring methods.
conduit
0.2–2.5 mm
½ in
provided two-terminal connectors.
conduit
Follow Class 1 wiring methods.
Maximum supported wire length between One-Cell luminaires and D1 Series
Wire Range/Specifications
2
(10 AWG) solid or
2
(22–6 AWG)
2
(24–14 AWG)
2
(6–14 AWG)
2
(26–14 AWG) using the
Strip
Torque Rating
Length
7 mm
0.8 Nm
(1/4 in)
(7 in-lb)
7 mm
0.5 Nm
(1/4 in)
(4.4 in-lb)
6.5 mm
0.5–0.6 Nm
(1/4 in)
(4.4–5.3 in-lb)
10 mm
4.0 Nm
(3/8 in)
(35 in-lb)
2
N/A
N/A
6 mm
0.4–0.5 Nm
(1/4 in)
(3.5–4.4 in-lb)
ArcSystem Installation Manual