Up-down mapping
Binary mapping
Parameterization
Display
38/54
Siemens
Building Technologies
• The multistate process value is mapped so that the mapping table specifies one or
more outputs to be driven.
• It is possible to have several active outputs, but only in a fixed combination.
• Examples: Enabling additional electrical heating or burner stages
MOValue
0
1
2
3
4
5
6
• The multistate process value is mapped so that the mapping table specifies one or
more outputs to be driven.
• It is possible to have several active outputs.
• Examples: Enabling additional electrical heating or burner stages
MOValue
0
1
2
3
4
:
63
In the case of bus failure, with DC 24 V module supply available, the following backup
states van be parameterized:
– No
(Inactive) (= default)
– Value (Active, Inactive)
– Keep
Same value as before the bus failure
Parameterization can be done during runtime.
• The I/O status LEDs indicate the activity of the relays
• In the case of an error the module status LED and all the I/O status LEDs assigned
to the function flash.
TX-I/O™ Module system – Functions and operation
Digital output functions
Stage
Active I/O points
0
None
1
n
2
n, n+1
3
n, n+1, n+2
4
n, n+1, n+2, n+3
5
n, n+1, n+2, n+3, n+4
6
n, n+1, n+2, n+3, n+4, n+5
Stage
n
n+1
0
0
0
1
1
0
2
0
1
1
1
3
4
0
0
:
63
1
1
Active I/O points
n+2
n+3
n+4
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
1
1
1
CM110561en_08
n+5
0
0
0
0
0
1
2018-10-25