Siemens TX-I/O TXM1.8D Functions And Operation page 33

Table of Contents

Advertisement

Note!
STOP
Response to failure
Failure
Address
key
Remote override
Display
Siemens
Building Technologies
Of course this only works if AC 24 V on the bus (conductor "
same transformer that supplies the source of the DC 24 V supply.
When backup value " Keep" is parameterized, the module is supposed to take no
activity at all, neither with absence nor with presence of bus or AC 24 V. Therefore, it
doesn't matter if bus terminal "V " (field device supply) is open or powered if there is a
bus connection module.
Modules of Series C actually work without AC 24 V connected.
With modules from Series D, however, it is compulsory to feed AC 24 V to bus terminal
"V " (field device supply) if there is a bus connection module. TXM1.6RL The module
always monitors this supply.
Simatic: It is also admissible to connect DC 24 V to bus conductor "V ".
As a summary, the I/O points behave as follows:
Bus
AC 24 V
X
X
X
X
X
Module type TXM1.6RL does not have a local override device, but remote override is
available for all I/O points.
• The I/O status LED is ON when the contact is closed.
• In the event of an error, the I/O status LED and the module status LED flash.
For details, especially in relation to flashing patterns and errors: refer to the section "Dis-
play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6].
TX-I/O™ Module system – Functions and operation
Digital output functions
Behavior of relays
Off
Backup
state
Masterdown
X
X
V
") comes from the very
Backup
Backup
delay
state
Powerdown
X
X
X
CM110561en_08
2018-10-25
33/54