2: More Information - Honeywell NOTIFIER LCD-160 Manual

Liquid crystal display
Table of Contents

Advertisement

Screen Displays
9.2.2 More Information
Pressing the soft key to the left of
the "More Information" screen. This screen contains additional information about the event shown
in the Event Reporting Format.
Lines 1- 4 - Event information displayed in the Event Reporting Format. See "Event Reporting
Format" on page 25.
Lines 6 through 9 - The Custom Action Message programmed for the point in alarm
Line 11 and 14 - These lines exist only for smoke/heat detectors. They do not display for wireless
smoke detectors.
Line 11
values:
Line 12
ALARM
1.66%, indicating the percent per foot obscuration value assigned to level 6.
PREALARM
value is 0.47%, indicating the percent per foot obscuration value assigned to level 3.
Line 13
ACTION
message that appears in this field depends on the drift compensation value. A detector will
automatically compensate for environmental contaminants and other factors over time, until
the tolerance value has been exceeded. The panel will signal a trouble condition when this
level has been reached. Refer to the following table for messages and required action.
36
MORE INFORMATION
A C K N O W L E D G E D F I R E A L A R M
E L E V A T O R L O B B Y
F I F T H F L O O R
1 1 : 5 8 : 4 5 A
T U E J A N 1 2 , 2 0 1 6
C A L L 2 0 3 - 5 5 5 - 1 2 1 2
G O T O A L A R M S I T E A N D I N V E S T I G A T E
A P P R O A C H T H E A L A R M L O C A T I O N W I T H C A U T I O N
B R I N G C E L L P H O N E A N D R E P O R T W H E N O N S I T E
V A L U E S : 1 2 1 % O F A L A R M , 1 4 5 % O F P R E A L A R M
A L A R M : 6 = 1 . 6 6 % , P R E A L A R M : 3 = 0 . 4 7 %
A C T I O N / S T A T U S : N O N E / V E R Y C L E A N
P E A K S : 5 6 % V E R I F Y C O U N T : 0 2 C O - O P : D 1 0 0 , 1 5 8
1 2 : 2 2 : 3 4 P
Figure 9.9 More Information Screen
This field gives the detector reading as it relates to its preprogrammed
121%
-
OF ALARM
alarm level value (indicated in the next line on the screen). The example above shows the
detector exceeding the alarm level by 21%.
This field gives the detector reading as it relates to its
145%
-
OF PREALARM
preprogrammed prealarm level value (indicated in the next line on the screen). The
example above shows the detector exceeding the prealarm level by 45%.
Six is the preprogrammed alarm level value for this detector: its value is
: 6=1.66% -
Three is the preprogrammed pre-alarm level value for this detector: its
: 3=0.47% -
/
:
/
STATUS
NONE
VERY CLEAN
on the "Event Counts Display" brings up
E A S T W I N G
Z 0 0 5
S M O K E ( P H O T O )
M O R E I N F O R M A T I O N
T U E J A N 1 2 , 2 0 1 6
This displays the maintenance status of the device. The
-
LCD-160 Manual — P/N 51850:D2 10/07/2016
Operating Screens
N 1 1 2 L 0 3 D 0 5 2
B A C K

Hide quick links:

Advertisement

Table of Contents
loading