Honeywell Control Box - Riello RL 190/M Installation, Use And Maintenance Instructions

Light oil burner
Table of Contents

Advertisement

3.11 Honeywell control box

Configuration jumpers
Purge timer
Sequence status led panel
Reset button
Keyboard display
module
APPLICATION
The Honeywell RM7840 ... Relay Modules are microprocessor-
based integrated burner controls for automatically fired gas, oil, or
combination fuel single burner applications.
The RM7840 ... Relay Modules are used for UL/CSA Modulating
and FM/IRI
Modulating burner applications. The RM7840 ... system consists of
a Relay Module. Keyboard Display Modules (standard with
RM7800), Dust Cover (standard with RM7840 ...), Subbase, Ampli-
fier, and Purge Card. Options include Personal Computer Inter-
face, DATA CONTROLBUS MODULE™, Remote Display
Mounting First-Out Expanded Annunciator and Combustion Sys-
tem Manager™ Software.
Functions provided by the RM7840 ... include automatic burner se-
quencing, flame supervision, system status indication, system or
self-diagnostics and troubleshooting.
20051197
Technical description of the burner
Wiring subbase
Run/test switch
Relay module
S8158
12
SPECIFICATIONS
Electrical ratings
Voltage and Frequency:
Power Dissipation:
Maximum Total
Connected Load:
Fusing:
Environmental ratings
Ambient Temperature
Operating:
Storage:
Humidity:
Vibration:
GB
Captive mounting
screw
Flame amplifier
RM7840 ...—120 Vac (+10/-15%),
50 or 60 Hz (±10%)
RM7840 ...: 10W maximum in the
Run mode
2000 VA
15A maximum, Type SC or
equivalent Fast Blow
-40°F to +140°F (-40°C to +60°C)
-40°F to +150°F (-40°C to +66°C)
85% relative humidity continuous,
noncondensing
0.5G environment
Fig. 7

Advertisement

Table of Contents
loading

This manual is also suitable for:

20050171