Audible Alerts; Coverage Patterns; Ultrasonic Sensor - LEGRAND WattStopper UW-100 Installation Instructions Manual

Ultrasonic wall switch occupancy sensor
Hide thumbs Also See for WattStopper UW-100:
Table of Contents

Advertisement

Visible Alert
The UW sensor can provide a visual alert as a warning one minute before the
load turns OFF.
Visible (DIP #5 ON)
No Visible
(DIP #5 OFF)

Audible Alerts

The UW can provide audible alerts as a warning before the load turns OFF.
Audible Alerts
(DIP #6 ON)
No Alerts

COVERAGE PATTERNS

Coverage testing
has been performed
according to the NEMA
WD 7 guideline. For
best performance, use
in spaces not larger
than 15' x 15'.

Ultrasonic Sensor

The sensor has two
ultrasonic transceivers
operating at 40kHz.
Detection sensitivity
can be adjusted using
the trimpot under the
ON/OFF buttons.
When only one minute is left in the time delay, the load
connected to the relay turns OFF for one second. This
provides a one minute warning before the load(s) are
turned OFF by the sensor.
No visual alert for delay expiration warning.
Unit will beep at one minute*, at 30 seconds and at 10
seconds before turning OFF load. When Walk-Through
is active, the unit beeps three times at 10 seconds
before the load goes OFF.
*If Visible Alert is also ON, the one-minute time-out
warning beep is replaced by the visible alert.
No warnings provided.
Top View
UW sensor coverage pattern
Call 800.879.8585 for Technical Support
Major motion
Minor motion
Ultrasonic
Coverage
20'
(6.1m)
15'
(4.5m)
7.5'
(2.2m)
10'
(3.0m)