Blown Fuse Detection - ABB PVS980-58 Firmware Manual

Central, from 1818 to 2091 kva
Table of Contents

Advertisement

activated after a delay defined in parameter
configuration limits contain additional parameters. See the following description.
The inverter can be configured to use either a relative or absolute comparison between DC
input currents by setting parameter
value that the individual currents are compared against is the reference value depending
on which type is selected by parameter
be selected to be either the maximum or the mean value of the connected DC inputs.
Global reference – selects the method for calculating reference current: from the input
section specific currents or from all inputs currents (global).
If all inputs have equal number of panels and are installed in a similar way, global
reference can be used.
If there are installation differences between the inputs, local reference should be used
because the input currents are comparable only inside the input section.
Relative comparison mode – individual DC input currents are compared against the
reference value in percent. The limit is defined by parameter
If a DC input current is more or less than the reference value an action is triggered after
the delay. Additionally, the reference value must be more than what is defined in
parameter
174.21 Relative threshold
Absolute mode – individual DC input currents are compared against the reference value
in amperes. If the difference is greater than the value found in parameter
in amperes an action is triggered after the delay.
current limit
Settings
174.15 Current deviation action
174.16 Comparison mode
174.17 Reference type
174.18 Global reference
174.19 Relative current limit
174.20 Absolute current limit
174.21 Relative threshold

Blown fuse detection

The Fuse monitor action can be enabled through parameter
The default action is Warning.
A blown fuse can be detected if the DC input current is less than the value found in
parameter
174.23 Blown fuse detection limit
Blown fuse active
boundary.
Note: It is also possible to check the DC fuse status with option G420: DC input
fuse blown indicator (one common output signal per power section, not with
0F291).
Settings
174.22 Fuse monitor action
174.23 Blown fuse detection limit
174.24 Blown fuse active boundary
174.15 Current deviation
174.16 Comparison mode
174.17 Reference
to avoid nuisance trips at low currents.
and the mean DC input current is over
delay. The
to the desired manner. The
type. The reference value can
174.19 Relative current
174.20 Absolute
174.22 Fuse monitor
Program features 41
limit.
action.