External grid monitoring relay

Depending on the installation, an external third party-certified grid monitoring relay may be
used. If an external relay is used, loose limits for grid monitoring should be set. The
recommended setting for the overvoltage monitoring limit is 130%. The limit for
undervoltage monitoring should be set as less than the external relay setting.
The inverter can use external grid monitoring through the parameter
that can be written, e.g., by fieldbus. If this parameter has a value of 1, external grid
monitoring indicates an unstable grid.
Settings
Parameter:135.16 External trip

Fault ride-through tripping curve

The fault ride-through (FRT) tripping curve function is an extra undervoltage and
overvoltage tripping function. The function programs a curve where the inverter
disconnects from the grid. The grid codes define the inverter behavior during a grid fault.
Typically, they specify the following:
how long a dip can last for
how long a swell can last for
how to behave with symmetrical voltage dips and peaks
how to behave with asymmetrical voltage dips and peaks.
There are two different cases of FRT function:
Low-voltage ride-through (LVRT), see page
High-voltage ride-through (HVRT), see page 22.
The FRT function can be enabled with parameter
Low-voltage ride-through (LVRT) tripping curve
U
U
n
126.10 Lv Rt trig U %
Figure 4. Low-voltage ride-through (LVRT) tripping curve
If the grid voltage drops below the low-voltage ride-through triggering level defined by
parameter
126.10 Lv Rt trig U
lasts longer than the voltage dependent time defined by parameters
time...126.28 Lv Rt ext U %,
without interruptions after the LVRT event has ended.
LVRT event starting point
sec1
sec2
sec3 sec4
Section durations
%, the inverter indicates a grid warning. If the grid transient
the inverter trips. Otherwise the inverter operates normally
135.16 External trip
and
21
126.01 FRT enable.
sec5
Starting and final voltage
levels for different sections
126.12 Lv Rt sec 1
Normal operating area
Program features 21