Customer I/O; Mv Station Monitoring And Control - ABB PVS980-58 Firmware Manual

Central, from 1818 to 2091 kva
Table of Contents

Advertisement

Customer I/O

MV station monitoring and control

Medium voltage station monitoring and control feature can be configured to protect the
transformer and to control the medium voltage switchgear. The software features to IOs
can be configured with parameters in group
following sections:
Digital
For details of the I/O connections, refer to the Hardware manual and Commissioning and
maintenance manual.
Digital inputs
There are eight configurable protective digital input features for medium voltage
transformer and for medium voltage switchgear:
Transformer temperature alarm
Transformer temperature fault
Transformer over pressure
Transformer low oil level
Transformer vacuum failure
Transformer gas discharge fault
Breaker opening
Phase loss detection.
Any of these features can be configured to use any of the customer interface digital inputs
of the inverter. For actual connections of digital inputs, refer to the Hardware manual.
Each configured digital input feature has the following set of parameters:
Parameter type
Source
Input action
Action delay
50 Program features
177 MV
inputs,
Analog inputs
Selection list
Off [0]
On [1]
Digital input X20.1 [2]
Digital input X20.2 [3]
Digital input X20.3 [4]
Digital input X20.4 [5]
Digital input X20.5 [6]
Digital input X20.6 [7]
Digital input X20.7 [8]
Spare DI8 [9]
Spare DI9 [10]
Spare DI10 [11]
Spare DI11 [12]
Spare DI12 [13]
No action [0]
Delayed warning [1]
Warning and delayed fault [2]
Delayed fault [3]
Fault and delayed MV breaker opening [4]
Delayed action defined in the above action parameters
Station. See descriptions in the
and
Digital
output.
0X20 terminal
Not supported
in this release.