h Selection
Telegrams TP -> RF
Group telegrams
Order No. 5110 00
TP and RF
only TP
only RF
transmit unfiltered
Software "Media coupler / repeater"
i Locking or forwarding group
telegrams, physically addressed
telegrams and broadcast telegrams
(routing) are not affected by the
configuration lock. With the safe-
state mode, the configuration lock
can be temporarily cancelled in
media coupler operation (see
page 25).
The media coupler can be programmed
and read out for diagnostic purposes
from the TP or RF side with no
limitation.
The media coupler can only be
programmed and read out via the TP
side. Physically addressed connections
reaching the device via the RF side are
not responded to. Nor does the device
respond to RF broadcast telegrams.
The media coupler can only be
programmed and read out via the RF
side of the corresponding domain.
Physically addressed connections
reaching the device via the TP side are
not responded to. Nor does the device
respond to TP broadcast telegrams.
i If the device is working exclusively
as a KNX RF repeater, it is only
possible to program the application
program and read out device
information via the RF side! In this
case, the parameter "Configuration
via" is permanently set to "only RF".
This parameter determines whether
group telegrams are forwarded from the
higher-level TP line to the lower-level RF
line (routing TP -> RF).
All group telegrams will be transmitted.
The filter table will be disregarded.
This setting influences the behaviour of
the red status LED. As soon as this
parameter is set to "forward unfiltered",
the status LED flashes red quickly.