Internal diagnosis
Electronics exchange
10
6
Diagnostics and servicing
6.1
Behaviour in case of failure
The instrument is permanently monitored by an internal diagnostic
system. If a malfunction is detected, the respective output signals
change to the safe status (see section "Safe status").
This condition is maintained for at least 1 second. If an error is no
longer detected, the safety function is performed correctly again.
The diagnosis interval is specified in chapter "Safety-related charac-
teristics".
If failures are detected, the entire measuring system must be shut
down and the process held in a safe state by other measures.
The manufacturer must be informed of the occurrence of a dangerous
undetected failure (incl. fault description).
6.2
Repair
The procedure is described in the operating instructions manual. Note
the instructions for setup.
SITRANS LVL200H - Safety Manual