Download Print this page

Zibro S13 Series Installation Manual page 78

Hide thumbs Also See for S13 Series:

Advertisement

instal_S(C)13xx.qxd
06-05-2010
4.
Insulate unused cords (conductors) with PVC-tape. Make sure they do not touch any electrical or metal
parts.
Fig. 26
AIR PURGING (for S 13xx models)
Air and moisture that remain in the refrigerant system, e.g. after installation, can cause undesirable effects
or damage as indicated below:
Pressure in the system rises.
Operating current rises.
Cooling or heating efficiency drops.
Moisture in the refrigerant circuit may freeze and block capillary tubing.
Water may lead to corrosion of parts in the refrigeration system.
Damage of the compressor.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must always be leak tested and
evacuated with aid of a vacuum pump to remove any noncondensables and moisture from the system.
PIPE LENGTH AND REFRIGERANT AMOUNT (for S 13xx models)
Connective pipe
lenght
Less than 5m
5~10m
When relocate the unit to another place, perform evacuation using vacuum pump.
Make sure the refrigerant added into the air conditioner is in liquid form in any case.
Only use the type of refrigerant as stated on the rating label.
ELECTRICAL SAFETY CHECK AND GAS LEAK CHECK
It is advised to do the following safety checks.
Electrical safety check
Perform the electric safe check after completing installation:
1.
Insulated resistance
The insulated resistance must be more than 2MΩ.
2.
Grounding work
After finishing grounding work, measure the grounding resistance by visual detection and grounding
resistance tester. Make sure the grounding resistance is less than 4 Ω.
4
78
11:41
Pagina 78
Cover
Screw
Air purging method
Use vacuum pump.
Use vacuum pump.
Additional amount above rating label
amount of refrigerant to be charged
------------------------
Liquid side pipe diameter:
ø 6.35 (Pipe length-5)x30g

Advertisement

loading

This manual is also suitable for:

Sc13 series