Shutdown; Shutting Down The Dhw Cylinder; Shutting Down The Dhw Cylinder If There Is A Risk Of Frost; Controls - Buderus Logalux LTN Series Installation Instructions For Contractors

Dhw cylinder
Table of Contents

Advertisement

7

Shutdown

7.1

Shutting down the DHW cylinder

▶ Shut down the heating system ( operating instructions for the
control unit and the heat source).
7.2
Shutting down the DHW cylinder if there is a risk of
frost
NOTICE: Cylinder damage from frost!
We recommend that you leave the DHW cylinder in use
when you are away from home, if there is a risk of frost.
▶ Activate the holiday function on the control unit or
select the lowest domestic hot water temperature.
▶ Shut down the heating system ( operating instructions for the
control unit and the heat source).
▶ Close the shut-off valve for cold water inlet (EK).
DANGER: Risk of scalding from hot water!
▶ Let the DHW cylinder cool down sufficiently after
shutting it down.
▶ Open the drain valve.
▶ In order to vent the cylinder, open the air vent valve or the highest
draw-off tap.
NOTICE: Risk of cylinder damage through corrosion!
After draining, residual moisture can cause corrosion.
▶ Fully drain the DHW cylinder via the drain valve –
including the lowest part of the DHW cylinder.
▶ Let the inside dry out thoroughly and leave the
covers of the inspection apertures open.
▶ Fully drain the DHW cylinder and dry out the inside.
Logalux LTN/LTD/LTH/LF 400...3000 – 6 720 818 806 (2015/12)
8

Controls

8.1

Operating the control unit

▶ Observe the operating and installation instructions.
8.2

Control of steam-heated DHW cylinders

▶ Control steam-heated DHW cylinders on the steam side.
Control on the condensate side is not possible.
Since it is not possible to raise the condensate with
steam-heated DHW cylinders, the condensate has to be
drained via the collector.
▶ Align the collector horizontally.
In the case of controls with temperature controllers
without auxiliary energy, it is always necessary to have
pump circulation for steam-heated DHW cylinders.
▶ Carry out the installation in the cold water supply.
Shutdown
7
21