Application Guidelines
50 Hz data
Nominal
Model
tons 60 Hz
(50 Hz)
TR
CH290
25
CH485
40
Displacement at nominal speed: 2900 rpm at 50 Hz
Net weight with oil charge
TR: Ton of Refrigeration,
EER: Energy Efficiency Ratio
COP: Coefficient Of Performance,
Subject to modification without prior notification.
Technical specifications
Nominal cooling
Power
capacity
input
W
Btu/h
kW
73 200
249 800
22.50
116 400
397 300
35.65
Standard rating conditions: ARI standard
Refrigerant: R410A
Swept
COP
E.E.R.
volume
W/W
Btu/h/W
cm
/rev
3
3.25
11.10
276.2
3.26
11.13
442.60
Evaporating temperature: 7.2 °C
Condensing temperature: 54.4 °C
Displacement
Net weight
Oil charge
m
/h
dm
3
3
48.10
6.7
111.0
77.0
6.7
175.0
Superheat: 11.1 K
Subcooling: 8.3 K
FRCC.PC.026.A4.02
kg
7