Toshiba MMD-AP0481HF2UL Service Manual page 95

Multi type air-conditioner
Hide thumbs Also See for MMD-AP0481HF2UL:
Table of Contents

Advertisement

2
Each time
button is pushed, indoor
unit numbers in the control group change
cyclically. Select the indoor unit to change
settings for.
The fan of the selected unit runs and the louvers
start swinging. The indoor unit for change settings
can be confirmed.
3
Specify CODE No. [
] with "TEMP."
buttons.
4
Select SET DATA [
] with "TIME"
buttons.
5
Push
button. When the display changes
from flashing to lit, the setup is completed.
• To change settings of another indoor unit,
2
repeat from Procedure
.
• To change other settings of the selected indoor
3
unit, repeat from Procedure
.
Use
button to clear the settings. To make
settings after
button was pushed, repeat from
2
Procedure
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed,
flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While
is flashing, no operation of the
remote control is accepted.)
29-EN
Filter sign setting
According to the installation condition, the filter sign
term (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
1
2
3
4
5
6
(
).
3
• For the CODE No. in Procedure
, specify [01].
4
• For the [SET DATA] in Procedure
, select the SET
DATA of filter sign term from the following table.
SET DATA
Filter sign term
0000
None
0001
150 H
/
2500 H
0002
(Factory default)
0003
5000 H
/
0004
10000 H
Setting the level of dirtiness
for the filter
The time when the filter indicator lights can be changed
to half depending on the level of dirtiness.
Follow to the basic operation procedure
1
2
3
4
5
6
(
). Perform the operation.
• Specify [02] for the CODE No. in Procedure
4
• The SET DATA in Procedure
is [0001].
SET DATA
0000
0001
Filter sign term
Normal
Half
Group control
In a group control, a remote control can control up to
maximum 8 units.
The Outside Air Unit and indoor unit for air conditioning
cannot be controlled as a group.
• For wiring procedure and wires of the individual line
(Identical refrigerant line) system, refer to "Electrical
connection" in this Manual.
• Wiring between indoor units in a group is performed
in the following procedure.
• Connect the indoor units by connecting the remote
control wires from the remote control terminal blocks
(A, B) of the indoor unit connected with a remote
control to the remote control terminal blocks (A, B) of
the other indoor unit. (Non-polarity)
• For address setup, refer to the Installation Manual
attached to the outdoor unit.
– 15 –
12
Test run
Before test run
• Before turning on the power supply, carry out the following procedure.
1) By using 500 V-megger, check that resistance of 1 MΩ or more exists between the terminal block L to N
and the grounding.
If resistance of less than 1 MΩ is detected, do not run the unit.
2) Check the valve of the outdoor unit being opened fully.
• To protect the compressor at activation time, leave power-ON for 12 hours or more before operating.
• Do not press the electromagnetic contactor to forcibly perform a test run. (This is very dangerous because the
protective device does not work.)
• Before starting a test run, set addresses by following the Installation Manual supplied with the outdoor unit.
Execute a test run
• When a fan operation is to be performed for an individual indoor unit, turn off the power, short CN72 on the circuit
board, and then turn the power back on. (First set the operating mode to "fan," and then operate.) When the test
run has been performed using this method, do NOT forget to release the shorting of CN72 after the test run is
completed.
Operate the unit with the wired remote control as usual.
For the procedure of the operation, refer to the attached Owner's Manual to the outdoor unit.
A forced test run can be executed in the following procedure even if the operation stops by thermostat-OFF.
In order to prevent a serial operation, the forced test run is released after 60 minutes have passed and returns to
3
the usual operation.
.
CAUTION
Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices.
1
Push
button for 4 seconds or more. [TEST] is displayed on the display part and the selection
of mode in the test mode is permitted.
2
Push
button.
2, 4
3
1,5
30-EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmd-ap0721hf2ulMmd-ap0961hf2ul

Table of Contents