No.
Item
6
Fan control
7
Forced thermostat
OFF
8
Forced fan OFF
Outline of specifications
1) On the Outside Air Unit, HH tap only isprovided.
2) For 1 minute after operation start, the forced fan
OFF control is invalid.
3) There is no cool air discharge preventive control.
4) When refrigerant is recovered while cooling or fan
operation is selected, and when cooling oil is
recovered while heating operation is selected, the
fan continues operation.
However the priority is given to forced fan OFF
control
1) The thermostat is forcedly off by outdoor suction
temperature (TA).
• COOL: At TA < 66 ˚F [ 19 ˚C ]
• HEAT: At TA > 59 ˚F [ 15 ˚C ] or TA < 23 ˚F [ – 5 ˚C ]
2) The thermostat is forcedly off by outdoor suction
temperature (TA) and remote control setting
temperature (TS).
• COOL: At TA < TS + 5.4 ˚F [ + 3 ˚C ]
• HEAT: At TA > TS – 5.4 ˚F [ – 3 ˚C ]
1) The thermostat is forcedly off by outdoor suction
temperature (TA).
• COOL/FAN: At TA < 41 ˚F [ 5 ˚C ]
• HEAT: At TA < 23 ˚F [ – 5 ˚C ]
2) After fan-OFF status continued for 60 minutes, turn
on the fan for 1 minute.
The forced fan-OFF status continues or released by
outdoor suction temperature (TA) in this time.
<Release conditions>
• COOL/FAN: At TA ≥ 41 ˚F [ 5 ˚C ]
• HEAT: At TA ≥ 23 ˚F [ – 5 ˚C ]
3) Other forced fan OFF release conditions
• Operation stop
• Operation mode exchange
• T
est run mode
Case to use in SMMS-i
Operation
[˚C]
[–10]
mode
˚F
14
COOL
23 ˚F [ –5 ˚C]
23 ˚F [ –5 ˚C]
HEAT
FAN
Case to use in SMMS-e
Operation
[˚C]
[–10]
mode
˚F
14
COOL
23 ˚F [ –5 ˚C]
23 ˚F [ –5 ˚C]
HEAT
FAN
Outside temp.
[0]
[10]
[20]
32
50
68
41 ˚F [5 ˚C]
41 ˚F [5 ˚C]
TS +5.4 ˚F [3 ˚C]
TS +5.4 ˚F [3 ˚C]
FAN
TS –5.4 ˚F [–3 ˚C]
TS –5.4 ˚F [–3 ˚C]
HEAT
Outside temp.
[0]
[10]
[20]
32
50
68
41 ˚F [5 ˚C]
41 ˚F [5 ˚C]
TS +5.4 ˚F [3 ˚C]
TS +5.4 ˚F [3 ˚C]
FAN
TS –5.4 ˚F [ –3 ˚C]
TS –5.4 ˚F [ –3 ˚C]
HEAT
– 24 –
Remarks
Operation ready display
[30]
[40]
86
104
109 ˚F [43 ˚C]
109 ˚F [43 ˚C]
COOL
FAN
FAN
[30]
[40]
86
104
115 ˚F [46 ˚C]
115 ˚F [46 ˚C]
COOL
109 ˚F [43 ˚C]
109 ˚F [43 ˚C]
FAN
FAN
[50]
122
[50]
122