Toshiba MMD-AP0481HF2UL Service Manual page 57

Multi type air-conditioner
Hide thumbs Also See for MMD-AP0481HF2UL:
Table of Contents

Advertisement

(Check code detected by IPDU featuring in SMMS-e and SMMS-i outdoor unit)
Check code
Outdoor 7-segment display
Sub-code
01: Compressor 1
F13
02: Compressor 2
03: Compressor 3
01: Compressor 1
H01
02: Compressor 2
03: Compressor 3
01: Compressor 1
H02
02: Compressor 2
03: Compressor 3
01: Compressor 1
H03
02: Compressor 2
03: Compressor 3
01: Compressor 1
P04
02: Compressor 2
03: Compressor 3
01: Compressor 1
P07
02: Compressor 2
03: Compressor 3
#0:Element short circuit
#1:Position detection circuit trouble
#3:Motor lock trouble
#4:Motor current trouble
P22
#C:TH Sensor temperature trouble
#D:TH Sensor short circuit/release
trouble
#E:Vdc voltage trouble
∗Put in Fan IPDU No. in [#] mark
01: Compressor 1
P26
02: Compressor 2
03: Compressor 3
01: Compressor 1
P29
02: Compressor 2
03: Compressor 3
Note: The above check codes are examples only, and different check codes may be displayed depending on
the outdoor unit configuration
Display of receiving unit
TCC-LINK
Indicator light block
central control
or main remote
Operation Timer Ready
control
display
F
1
3
H
0
1
H02
H03
P
0
4
P
0
7
P
2
2
P
2
6
P
2
9
Typical problem site
Flash
Trouble in temperature
A
L
T
sensor built into indoor
IPM (TH)
C
o
m
p
e r
s s
r o
b
e r
a
k
d
o
w
n
Compressor trouble
(lockup)
Current detection circuit
trouble
Activation of high-pressure
A
L
T
SW
Heat sink overheating
A
L
T
trouble
A
L
T
Outdoor fan IPDU trouble
Activation of IPM
A
L
T
short-circuit protection
Compressor position
A
L
T
detection circuit trouble
– 57 –
Description of proplem
Temperature sensor built into indoor IPM (TH)
has been open/short-circuited.
Inverter current (Idc) detection circuit detects
overcurrent.
Compressor lockup is detected
Abnormal current is detected while inverter
compressor is turned off.
High-pressure SW is activated.
Temperature sensor built into IPM (TH) detects
overheating or has been short-circuited.
Outdoor fan IPDU detects trouble.
Short-circuit protection for compressor motor
driver circuit components is activated (momentary
overcurrent).
Compressor motor position detection trouble is
detected.