Address
Name
40308
THERMO_OUT_TRACKING_ERROR_PCT
40309
THERMO_OUT_POWER_PCT
40401
THERMO_SETUP_UNITTYPE
40402
THERMO_SETUP_SYSTEM_CONFIGURATION
40403
THERMO_SETUP_COMPRESSOR_MINIMUM_SPEED_HZ
40404
THERMO_SETUP_COMPRESSOR_MAXIMUM_SPPED_HZ
40405
THERMO_SETUP_DELTA_HZ_PER_SEC
40407
THERMO_SETUP_DELTA_TEMP
40409
THERMO_SETUP_OIL_LOSS_TRIG_TIME_SEC
40410
THERMO_SETUP_OIL_RETURN_SPEED_HZ
40411
THERMO_SETUP_OIL_RETURN_HOLD_TIME_SEC
40412
THERMO_SETUP_START_UP_SPEED_HZ
40413
THERMO_SETUP_START_UP_HOLD_TIME_SEC
40414
THERMO_SETUP_RESTART_TIME_SEC
40415
THERMO_SETUP_CANCEL_CENTER_HZ_1
40416
THERMO_SETUP_CANCEL_BANDWIDTH_HZ_1
40417
THERMO_SETUP_CANCEL_CENTER_HZ_2
40418
THERMO_SETUP_CANCEL_BANDWIDTH_HZ_2
40419
THERMO_SETUP_CANCEL_CENTER_HZ_3
40420
THERMO_SETUP_CANCEL_BANDWIDTH_HZ_3
40421
THERMO_SETUP_CANCEL_CENTER_HZ_4
40422
THERMO_SETUP_CANCEL_BANDWIDTH_HZ_4
40423
THERMO_SETUP_CANCEL_CENTER_HZ_5
40424
THERMO_SETUP_CANCEL_BANDWIDTH_HZ_5
40425
THERMO_SETUP_PI_COMPRESSOR_AC_KP
40427
THERMO_SETUP_PI_COMPRESSOR_AC_TN
40428
THERMO_SETUP_PI_COMPRESSOR_AC_TT
40429
THERMO_SETUP_PI_COMPRESSOR_HP_KP
40431
THERMO_SETUP_PI_COMPRESSOR_HP_TN
40432
THERMO_SETUP_PI_COMPRESSOR_HP_TT
41609
OUTDOOR_FAN_CAPACITY_PCT_MIN
41611
OUTDOOR_FAN_CAPACITY_PCT_MAX
41613
OUTDOOR_FAN_CONTROL_SIGNAL_FREQUENCY
40479
THERMO_SETUP_CRANK_CASE_HEATING_ON_TEMP
Table 6.2 Thermo Controller Register Overview (Node 162)
®
VLT
Inverter Scroll CDS 801 Operating Instructions
Description
If the compressor is running in external speed % control mode
the tracking error is calculated
The Tracking error is the difference between actual compressor
speed % and external speed % command
If not running external speed, the tracking error is set to 0
Actual Drive power in % of nominal power
Unit type:
0 = 3 Ton
1 = 4 Ton
2 = 5 Ton
System Configuration
1 = ID1 (not active)
2 = ID2 AC/HP reversible
3 = ID3 (not active)
4 = ID4 GSHP reversible
5 = ID5 (not active)
6 = ID6 AC only
Minimum compressor speed
Maximum compressor speed
Allowed speed rate of change in Hz pr. s
Delta temperature setting for fan "Delta T" control mode
When running below oil return speed for more than this time,
oil return is initiated
Defined oil return speed
Hold time for running at oil return speed
Start up speed for system
Hold time for start up speed
Minimum Time between repeated starts
Centre frequency #1 for speed range cancellation
Bandwidth #1 for speed range cancellation
Centre frequency #2 for speed range cancellation
Bandwidth #2for speed range cancellation
Centre frequency #3 for speed range cancellation
Bandwidth #3 for speed range cancellation
Centre frequency #4 for speed range cancellation
Bandwidth #4 for speed range cancellation
Centre frequency #5 for speed range cancellation
Bandwidth #5 for speed range cancellation
Proportional gain for AC compressor capacity controller
Integration time for AC compressor capacity controller
Tracking time constant for AC compressor capacity controller
Proportional gain for HP compressor capacity controller
Integration time for HP compressor capacity controller
Tracking time constant for HP compressor capacity controller
Minimum duty cycle that will be output by the fan controller
Maximum duty cycle that will be output by the fan controller
Set frequency of the condenser fan PWM signal
Ambient temperature where crankcase heating is activated
®
MG10V402 - VLT