General Information

Component Locations

OFF
ON
A
B
C
Figure 2-4. Component Locations
A

Battery disconnect switch

B

Battery status LED

C
Intake filter
D
Front cover
E
Exhaust vent
10
Battery Disconnect Switch
E
See
Figure
disconnects the battery string from the battery monitoring
system (BMS) electronics.
The Battery Disconnect must be locked in the OFF
position during installation. The switch bracket accepts a
standard lockout/tagout lock.
D
NOTE: Turn Battery Disconnect OFF whenever system
will be powered down and left inactive for an extended
period of time.
Battery Status LED
See
Figure
(B) communicates battery status.
LED State
Green, 3 sec
0009890
solid at power up
Red, 3 sec solid
at power up
Red/green,
alternating
Green, solid
Green, strobe
Green, rapid
flashing
Orange, solid
Orange, strobe
Red, strobe
Red, rapid
flashing
DANGER
Electrocution. Initiate a system-wide shutdown and turn
the PWRcell Disconnect Switch OFF on all connected
batteries before performing service. Failure to do so will
result in death, serious injury, equipment and property
damage.
2-4.
Battery
Disconnect
2-4. The color and strobing interval of LED
Table 2-1. Battery Status LED
Interpretation (strobe interval)
Enabled, operation starting
Disabled
Initializing, connecting battery and
REbus, system energizing
Enabled, charging
Enabled, standby (3 sec)
Enabled, discharging
Waiting
Asleep (8 sec)
Disabled (3 sec)
Error state
Installation Manual for Generac PWRcell Battery
(000600)
switch