Installing Rear Modules; Installing Grounding Tabs; Installing Front Modules - Generac Power Systems PWRcell Series Installation Manual

Table of Contents

Advertisement

Installing Rear Modules

See
Figure
4-7. Angle top of battery module (G)
1.
under and behind bracket lip (H).
NOTE: Battery module ports (I) must face the right side
of the PWRcell battery body with the COM ports above
the power port.
Slide bottom of module to back of PWRcell battery
2.
chassis (J).
Push bottom of module against grounding clips (K).
3.
NOTE: Grounding clips are designed to contact and bite
into the battery module case to provide an equipment
grounding connection.
H
G
Figure 4-7. Installing Rear Battery Modules

Installing Grounding Tabs

See
Figure
4-8. Install two L-shaped grounding
1.
tabs (L) at the bottom of the module on both sides.
Fasten each grounding tab with a M4x8 mm SEMS
2.
screw (M) torque to 13 in-lb (1.47 Nm).
L
Figure 4-8. Installing Bottom Grounding Tabs
Installation Manual for Generac PWRcell Battery
See
3.
top of the module on both sides.
Fasten each grounding tab with a M4x8 mm SEMS
4.
screw (M) and torque to 13 in-lb (1.47 Nm).
Figure 4-9. Installing Top Grounding Tabs

Installing Front Modules

See
Figure
the same procedure as used on the rear modules. See
Installing Rear Modules
I
J
K
009929
N
Figure 4-10. Installing Front Battery Modules
M
009930
Installing Generac PWRcell Battery
Figure
4-9. Install grounding tabs (L) at the
L
4-10. Install front battery modules (N) using
M
009932
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pwrcell 9Pwrcell 12Pwrcell 15Pwrcell 17

Table of Contents