2.2 Intended Use
The MGS-402 provides audio-visual alerts and information pertaining to the status of a centralized gas
detector network. This information allows concise, at-a-glance notification of any alarm or fault status
regarding a connected gas detector located outside the monitored space, as required by industry safety
standards (EN 378, ASHRAE 15).
2.3 Design Features
Power options
Output/
Communications
4
100 - 240 VAC, 50/60 Hz, 20 W (max.)
Provides power for up to (2) MGS-410 Bacharach gas detectors
RS485 Modbus RTU Master for Gas Detectors
RS485 Modbus RTU Slave for BMS
Diagnostic/status LEDs
•
Controller (power, fault)
•
Gas detectors (power, fault, low alarm, high alarm)
Configurable output options
•
3 × relays (fault, low alarm, high alarm)
•
2× Analog outputs (4-20 mA, 1-5 V or 2-10 V)
Integrated high output visual strobe
Integrated high output audible alarm
Remote silence input (In addition to silence on the on the controller input.)