Intended Use; Design Features - Bacharach MGS-402 User Manual

Gas detection controller for commercial & industrial applications
Table of Contents

Advertisement

MGS-402 User Manual
WARNING: This instrument is neither certified nor approved for operation in oxygen-enriched
atmospheres. Failure to comply may result in EXPLOSION.
WARNING: For your safety, DO NOT use this instrument in locations classified as hazardous
because it has not been designed for such areas.

2.2 Intended Use

The MGS-402 provides audio-visual alerts and information pertaining to the status of a centralized gas
detector network. This information allows concise, at-a-glance notification of any alarm or fault status
regarding a connected gas detector located outside the monitored space, as required by industry safety
standards (EN 378, ASHRAE 15).

2.3 Design Features

Power options
Output/
Communications
4
100 - 240 VAC, 50/60 Hz, 20 W (max.)
Provides power for up to (2) MGS-410 Bacharach gas detectors
RS485 Modbus RTU Master for Gas Detectors
RS485 Modbus RTU Slave for BMS
Diagnostic/status LEDs
Controller (power, fault)
Gas detectors (power, fault, low alarm, high alarm)
Configurable output options
3 × relays (fault, low alarm, high alarm)
2× Analog outputs (4-20 mA, 1-5 V or 2-10 V)
Integrated high output visual strobe
Integrated high output audible alarm
Remote silence input (In addition to silence on the on the controller input.)
1100-2570 Rev 1