INSTALLATION GUIDE
P/N: 6709-9002
Revision 0
January 25, 2016
Controller Housing
(4-6 Channels)
Controller Housing
(1-2 Channels)
CAUTION: DO NOT MOUNT the MGS
Controller in an area that may contain
flammable liquids or vapors. Opera-
tion of electrical equipment in such
an area constitutes a safety hazard.
WARNING: Strictly follow the instruc-
tions in the Controller Manual (part
number 6709-9000) available at
www.MyBacharach.com.
1: OPERATING AREA AND CONDITIONS
The Bacharach MGS Series controllers provide local
alarm status indications (via multi-colored, per-
channel LEDs) as well as common single-level or
dual-level digital (relay) alarm outputs based on 1, 2,
4, or 6 input signals and 1 or 2 user-definable
set-points.
MGS Controllers support multiple input sensors/
transmitters (1, 2, 4, or 6 channels) based on the
model of the controller. Inputs are standard 4-20 mA
signals from MGS-series sensors or any standard,
linear, 4-20 mA transmitter.
The instrument is powered 100V-230V AC (50-60Hz) or
12V DC (specified at time of order).
2: SAFETY INSTRUCTIONS
USER MANUAL: Before using this equipment,
carefully read and strictly follow the User
Manual (part number 6709-9000). The user
must fully understand and strictly observe the
instructions. Use the equipment only for the
purposes listed and under the conditions speci-
fied in those documents.
CODE COMPLIANCE: Comply with all local and
national laws, rules and regulations associated
with this equipment.
GENUINE PARTS: Use only genuine Bacharach
spare parts and accessories, otherwise proper
functioning of the equipment may be impaired.
TECHNICIAN USE ONLY: This unit must be
installed by a suitably qualified technician who
will install this unit in accordance with these
instructions and the standards in their particular
industry/country. Operators of the unit should
be aware of the regulations and standards in
their industry/country for the operation of this
unit. These notes are only intended as a guide
and the manufacturer bears no responsibility for
the installation or operation of this unit.
Failure to install and operate the unit in accor-
dance with these instructions and with industry
guidelines may cause serious injury including
death and the manufacturer will not be held
responsible in this regard.
SAFE MOUNTING: This controller must be
connected by a marked, suitably located and
easily reached switch or circuit-breaker as
means of disconnection.
3: MOUNTING
ENVIRONMENTAL CONSIDERATIONS: Care-
fully consider the full range of environmental
conditions to which the instruments will be
exposed.
APPLICATION CONSIDERATIONS: The specifics
of the application (for example, possible leaks,
air movement/draft, etc.) must be observed.
ACCESSIBILITY CONSIDERATIONS: The degree
of accessibility required for maintenance
purposes must be granted.
ACCESSORY CONSIDERATIONS: The types of
optional and accessory equipment that will be
used with the system must be kept in mind.
ELECTRONIC CONSIDERATIONS: The system
contains sensitive electronic components that
can be easily damaged. Do not touch nor
disturb any of these components.
Mount the MGS Controller according to the
above considerations, product dimensions (see
Section 4), and the maximum wiring lengths
(see Section 5).
4: DIMENSIONS
Screw
0.4 in (9.0 mm)
0.2 in
0.6 in
(5.0 mm)
(15.5 mm)
2.0 in
(50.0 mm)
0.4 in (10.0 mm)
1-2 Sensor
Controller
Housing
Screw
0.2 in
(4.8 mm)
0.6 in
(15.0 mm)
2.9 in (74.5 mm)
0.5 in (12.7 mm)
0.5 in (12.7 mm)
10.26 in (260.50mm)
5.13 in (130.25 mm)
O 0.20 in (5.10 mm)
Mounting
Hole
4-6 Sensor
Controller Housing
O 0.18 in (4.60 mm)
9.55 in (242.50 mm)
5: WIRING
CABLE OPENINGS: The metal controller housing
provides a number of PG7 openings for cable glands
or plugs.
Refer to the
User Manual (part number
9000)
at www.MyBacharach.com for detailed
instructions on accessing the internal components
for wiring.
WARNING: The mains power supply
cable should be of an approved type
based on local regulations. Connection
to the mains power supply must be
made via an approved, readily-
accessible, switched and fused plug and
socket (or as per local wiring regula-
tions) which should be within 19 feet (3
meters) of the sesnor/transmitter.
SHIELD WIRE WARNING: Connect the
shield of the power wires to the earth
ground of the central control system
(e.g., chassis, ground bus bar, etc.).
1: Strip 0.2 to 0.25 inches (5 to 7 mm)
of wiring insulation.
0.6 in (15.0 mm)
2: Connect the wires as indicated.
Refer to the Controller manual (part
number 6709-9000) at
www.MyBacharach.com for additional
wiring configurations.
NOTE: After wiring is completed,
carefully re-assemble the enclosure and
its components.
World Headquarters
621 Hunt Valley Circle
New Kensington, PA 15068 USA
Phone: 724-334-5000 • Fax: 724-334-5001
Toll Free: 1-800-736-4666
Website: www.MyBacharach.com
E-mail: help@MyBacharach.com
114A Georges Street Lower
Dun Laoghaire • Co Dublin • Ireland
Phone: +353 1 284 6388 • Fax: +353 1 284 6389
6709-

Advertisement

loading
Need help?

Need help?

Do you have a question about the MGS Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bacharach MGS Series

  • Page 1 ACCESSORY CONSIDERATIONS: The types of optional and accessory equipment that will be 4-6 Sensor used with the system must be kept in mind. The Bacharach MGS Series controllers provide local Controller Housing alarm status indications (via multi-colored, per- ELECTRONIC CONSIDERATIONS: The system...
  • Page 2 2 Sensor 1 Alarm Confirguration 2 Sensor 2 Alarm Confirguration Relay Relay 2 High V IN Alarm RESET Alarm Relay SENSOR 2 Relay SENSOR 2 V IN 4-20mA OUT FAIL FAIL SAFE SAFE 4-20mA OUT Sensor Unit Sensor Unit SENSOR 1 SENSOR 1 Relay 1 Alarm...