Section 1. Introduction 1.1. Overview The MGS Series controllers provide local alarm status indications (via multi-colored, per-channel LEDs) as well as single-level or dual-level digital (relay) alarm outputs based on 1, 2, 4, or 6 input signals and 1 or 2 user-definable set-points.
Page 7
MGS Series Controller Manual Figure 2. Sample Configurations (4,6-Channel) MGS Controllers have either one or two relay outputs: one for single- level alarm controllers (“Alarm”), and 2 for dual-level alarm controllers (“Alarm High” and “Alarm Low”). Unlike the alarm LEDs that provide a channel-by-channel alarm status of each incoming transmitter’s signal,...
MGS Series Controller Manual For dual-alarm configurations, the Alarm Low relay output “trips” or “energizes” if any of the inputs exceed the alarm threshold set by the low alarm pot. Similarly, the Alarm High relay output “trips” or “energizes” if any of the inputs exceed the alarm threshold set by the high alarm pot.
MGS Series Controller Manual Section 2. Mounting Instructions 2.1. Installation Warnings WARNING: Explosion hazard! Do not mount the MGS Controller in an area that may contain flammable liquids, vapors, or aerosols. Operation of any electrical equipment in such an environment constitutes a safety hazard.
Heavy localized exhaust fumes (carbon monoxide, dioxide, propane) from engine-driven forklifts in confined spaces or close to sensors. Bacharach recommends setting the alarm delay to minimize false alarms. See Section 4.7 for more information. 2.3. Mounting Dimensions The controllers contain a single teardrop cutout at the top center of the enclosure.
MGS Series Controller Manual Section 3. Wiring 3.1. 1- and 2-Channel Units (Single- and Dual-Alarm) Controller Controller Sensor/ Signal Terminal Block Pin Number Transmitter +Ve supply +V in Sensor 4-20 mA signal 4-20 mA out Connections -Ve input GND in Figure 5.
MGS Series Controller Manual Figure 6. Wiring (2-Channel, Dual-Alarm Unit Shown) 3.2. 4- and 6-Channel Units (Single- and Dual-Alarm) Wiring to Sensors Controller Controller Sensor/ Signal Terminal Block Pin Number Transmitter +Ve supply +V in CN1 – CN6 4-20 mA signal...
Page 16
MGS Series Controller Manual Figure 7. Wiring (6-Channel, Single-Alarm Unit Shown) 6709-9000 Rev 2 0.561.8187 information@itm. www. .com...
Page 17
MGS Series Controller Manual Figure 8. Wiring (6-Channel, Dual-Alarm Unit Shown) NOTE: An external horn is provided with 4- and 6-channel units. Refer to the next section for details. 6709-9000 Rev 2 0.561.8187 information@itm. www. .com...
MGS Series Controller Manual 3.3. External Horn (for Audible Alarms) ° Horn Specifications (Test Conditions at 25 Specification Description Housing Black ABS Power Rating 10 W (RMS), 15 W (peak) Voltage 12 VDC (Rated), 6-16 VDC range Current 200 mA max (@ 12 VDC)
MGS Series Controller Manual Section 4. Configuration and Operation 4.1. Overview The following topics are explained in this section: • Changing alarm limits (pots and CAL header) • Fail-safe operation (jumper) • Muting the audible alarm (key) • Resetting high alarms (button) 4.2.
MGS Series Controller Manual 4.3. Changing Alarm Level for 2-Channel, 1-Alarm Units Step Instructions Connect voltmeter leads to the GND test point and HIGH test point. Using the flat-blade screwdriver, adjust the corresponding HIGH potentiometer until the reading on the DC voltmeter corresponds to the desired input alarm level.
MGS Series Controller Manual 4.4. Changing Alarm Level for 2-Channel, 2-Alarm Units Step Instructions Connect voltmeter leads to the GND test point and HIGH test point. Using the flat-blade screwdriver, adjust the corresponding HIGH potentiometer until the reading on the DC voltmeter corresponds to the desired input high alarm level.
MGS Series Controller Manual NOTE: Both channels have the same alarm thresholds. 4.5. Changing Alarm Level for 6-Channel, 1-Alarm Units Step Instructions Connect voltmeter leads to the GND test point and HIGH test point. Using the flat-blade screwdriver, adjust the corresponding HIGH potentiometer until the reading on the DC voltmeter corresponds to the desired input alarm level.
MGS Series Controller Manual 4.6. Changing Alarm Level for 6-Channel, 2-Alarm Units Step Instructions Connect voltmeter leads to the GND test point and HIGH test point. Using the flat-blade screwdriver, adjust the corresponding HIGH potentiometer until the reading on the DC voltmeter corresponds to the desired input high alarm level.
MGS Series Controller Manual 4.7. Output Delays There is a fixed delay between the sensor output indicating an alarm and the controller registering this alarm condition as valid. This is to prevent false alarms on transient outputs. This delay period is fixed and is approximately 25 seconds for the low level and then another 25 seconds for the high level.
MGS Series Controller Manual 4.10. Resetting High Alarms (Dual-Level Units Only) The red pushbutton on the controller is used to acknowledge (reset) high alarms. Once the unit goes into a high alarm state the alarm latches. After the gas has cleared the reset button must be pushed to clear the alarm(s).
MGS Series Controller Manual ECLARATION OF ONFORMITY The manufacturer of Bacharach, Inc. the products covered 621 Hunt Valley Circle by this declaration: New Kensington, PA 15068 Year conformity is 2014 (IEC/EN61010), 2011 (EN61326) declared: Product(s): Model(s): MGS Controller The undersigned hereby declares that the above referenced products are in conformity with the provisions of the following standard(s) and is in accordance with the following directive(s).