Bacharach MGS SERIES Installation And Operation Manual

Multi-channel input single- and dual-alarm controllers
Hide thumbs Also See for MGS SERIES:

Advertisement

Multi-Channel Input
Single- and Dual-Alarm
Controllers
Installation and Operation Manual
Instruction 6709-9000
Revision 1 – October 25, 2012
Product Leadership • Training • Service • Reliability

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MGS SERIES and is the answer not in the manual?

Questions and answers

Summary of Contents for Bacharach MGS SERIES

  • Page 1 Multi-Channel Input Single- and Dual-Alarm Controllers Installation and Operation Manual Instruction 6709-9000 Revision 1 – October 25, 2012 Product Leadership • Training • Service • Reliability...
  • Page 2 INSTRUMENT REQUIRE NON-WARRANTY REPAIR, YOU MAY CONTACT THE DISTRIBUTOR FROM WHOM IT WAS PURCHASED OR YOU MAY CONTACT BACHARACH DIRECTLY. IF BACHARACH IS TO DO THE REPAIR WORK, SEND THE INSTRUMENT, PREPAID, TO BACHARACH, INC. AT THE FOLLOWING ADDRESS. BACHARACH, INC.
  • Page 3 AND ALL RIGHTS ARE RESERVED. NO PARTY MAY USE OR COPY SUCH SOFTWARE IN ANY MANNER OR FORMAT, EXCEPT TO THE EXTENT THAT BACHARACH GRANTS THEM A LICENSE TO DO SO. IF THIS SOFTWARE IS BEING LOADED ONTO MORE THAN ONE COMPUTER, EXTRA SOFTWARE LICENSES MUST BE PURCHASED.
  • Page 4: Table Of Contents

    MGS Series Controller Manual Table of Contents SECTION 1. INTRODUCTION ................ 5 1.1. O ....................5 VERVIEW 1.2. 2-C ............. 5 HANNEL AND HANNEL ODELS 1.3. A ....................5 LARMING 1.4. C ....................8 OMPONENTS 1.5. S ..................11 PECIFICATIONS SECTION 2.
  • Page 5: Introduction

    Section 1. Introduction 1.1. Overview The MGS Series controllers provide local alarm status indications (via multi-colored, per-channel LEDs) as well as single-level or dual-level digital (relay) alarm outputs based on 1, 2, 4, or 6 input signals and 1 or 2 user-definable set-points.
  • Page 6 MGS Series Controller Manual Figure 1. Sample Configurations (1,2-Channel) 6709-9000 Rev 1...
  • Page 7 MGS Series Controller Manual Figure 2. Sample Configurations (4,6-Channel) MGS Controllers have either one or two relay outputs: one for single- level alarm controllers (“Alarm”), and 2 for dual-level alarm controllers (“Alarm High” and “Alarm Low”). Unlike the alarm LEDs that provide a channel-by-channel alarm status of each incoming transmitter’s signal,...
  • Page 8: Components

    MGS Series Controller Manual Figure 3. Sample Front Panels Showing Status LEDs For dual-alarm configurations, the Alarm Low relay output “trips” or “energizes” if any of the inputs exceed the alarm threshold set by the low alarm pot. Similarly, the Alarm High relay output “trips” or “energizes” if any of the inputs exceed the alarm threshold set by the high alarm pot.
  • Page 9 MGS Series Controller Manual Components Descriptions Power input Provides power to the MGS Controller Power LED Power status indicator Channels (max) 1-2 Channel Units 4-6 Channel Units Sensor input(s) max 2 max 6 max Alarm levels Single Dual Single Dual...
  • Page 10 MGS Series Controller Manual NOTE: Figure 4 shows components associated with a dual- alarm configuration. For single-alarm configurations, the Low Alarm LEDs are not present. JP1 on the single-alarm configuration is the delay jumper. Figure 5. 2-Channel, Dual-Alarm MGS Controller NOTE: Figure 5 shows components associated with a dual- alarm configuration.
  • Page 11: Specifications

    MGS Series Controller Manual 1.5. Specifications Specification 1-2 Channel 4-6 Channel Product Type 1-2 channel alarm 4-6 channel alarm controller controller Max Channels Inputs 4-20 mA 4-20 mA Display LED alarm indicators LED alarm indicators Ambient -20 to +50 degrees C...
  • Page 12: Mounting Instructions

    MGS Series Controller Manual Section 2. Mounting Instructions 2.1. Installation Warnings WARNING: Explosion hazard! Do not mount the MGS Controller in an area that may contain flammable liquids, vapors, or aerosols. Operation of any electrical equipment in such an environment constitutes a safety hazard.
  • Page 13: Mounting Dimensions

    Heavy localized exhaust fumes (carbon monoxide, dioxide, propane) from engine-driven forklifts in confined spaces or close to sensors. Bacharach recommends setting the alarm delay to minimize false alarms. See Section 4.7 for more information. 2.3. Mounting Dimensions The controllers contain a single teardrop cutout at the top center of the enclosure.
  • Page 14 MGS Series Controller Manual Figure 6. Mounting Dimensions (2-Channel Unit) 6709-9000 Rev 1...
  • Page 15 MGS Series Controller Manual Figure 7. Mounting Dimensions (6-Channel Unit) 6709-9000 Rev 1...
  • Page 16: Wiring

    MGS Series Controller Manual Section 3. Wiring 3.1. 1- and 2-Channel Units (Single- and Dual-Alarm) Wiring to Sensors/Transmitters Controller Controller Sensor/ Signal Terminal Block Pin Number Transmitter +Ve supply +V in 4-20 mA signal 4-20 mA out -Ve input GND in...
  • Page 17: 4- And 6-Channel Units (Single- And Dual-Alarm)

    MGS Series Controller Manual NOTE: The potential from -Ve to +Ve is approximately 15 VDC. Figure 9. Wiring (2-Channel, Dual-Alarm Unit Shown) 3.2. 4- and 6-Channel Units (Single- and Dual-Alarm) Wiring to Sensors Controller Controller Sensor/ Signal Terminal Block Pin Number...
  • Page 18 MGS Series Controller Manual Figure 10. Wiring (6-Channel, Single-Alarm Unit Shown) 6709-9000 Rev 1...
  • Page 19: E Xternal

    MGS Series Controller Manual Figure 11. Wiring (6-Channel, Dual-Alarm Unit Shown) NOTE: An external horn is provided with 4- and 6-channel units. Refer to the next section for details. 6709-9000 Rev 1...
  • Page 20: External Horn (For Audible Alarms)

    MGS Series Controller Manual 3.3. External Horn (for Audible Alarms) ° Horn Specifications (Test Conditions at 25 Specification Description Housing Black ABS Power Rating 10 W (RMS), 15 W (peak) Voltage 12 VDC (Rated), 6-16 VDC range Current 200 mA max (@ 12 VDC)
  • Page 21: Configuration And Operation

    MGS Series Controller Manual Section 4. Configuration and Operation 4.1. Overview The following topics are explained in this section: • Changing alarm limits (pots and CAL header) • Setting output delays (jumper) • Fail-safe operation (jumper) • Muting the audible alarm (key) •...
  • Page 22 MGS Series Controller Manual POTs Used to Set Alarm Limits Max # Number of Input Alarm Type Alarms Chans High High High High The alarm range is set over the voltage range of 0.4 V to 2.0 V. A voltage of 0.4 V equals 0 ppm and 2.0 V equals full scale such as 1000 ppm.
  • Page 23: Changing Alarm Level For 2-Channel, 1-Alarm Units

    MGS Series Controller Manual 4.3. Changing Alarm Level for 2-Channel, 1-Alarm Units Step Instructions Connect voltmeter leads to pin 4 (-Ve) and pin 1 (+Ve) on the CAL header. Using the flat-blade screwdriver, adjust potentiometer P3 until the reading on the DC voltmeter corresponds to the desired input alarm level.
  • Page 24: Changing Alarm Level For 2-Channel, 2-Alarm Units

    MGS Series Controller Manual 4.4. Changing Alarm Level for 2-Channel, 2-Alarm Units Step Instructions Connect voltmeter leads to pin 4 (-Ve) and pin 1 (+Ve) on the CAL header. Using the flat-blade screwdriver, adjust potentiometer P7 until the reading on the DC voltmeter corresponds to the desired input high alarm level.
  • Page 25: Changing Alarm Level For 6-Channel, 1-Alarm Units

    MGS Series Controller Manual 4.5. Changing Alarm Level for 6-Channel, 1-Alarm Units Step Instructions Connect voltmeter leads to pin 4 (-Ve) and pin 1 (+Ve) on the CAL header. Using the flat-blade screwdriver, adjust potentiometer P7 until the reading on the DC voltmeter corresponds to the desired input alarm level.
  • Page 26: Changing Alarm Level For 6-Channel, 2-Alarm Units

    MGS Series Controller Manual 4.6. Changing Alarm Level for 6-Channel, 2-Alarm Units Step Instructions Connect voltmeter leads to pin 4 (-Ve) and pin 1 (+Ve) on the CAL header. Using the flat-blade screwdriver, adjust potentiometer P7 until the reading on the DC voltmeter corresponds to the desired input high alarm level.
  • Page 27: Output Delays

    MGS Series Controller Manual 4.7. Output Delays Controllers with only single-level alarm capabilities use jumper JP1 to enable/disable a 3-minute output delay for the input level alarm. This delay provides a hysteresis preventing nuisance toggling of the alarm. The delay is enabled when the jumper is in the ON position, and disabled when in the OFF position.
  • Page 28: Fail Safe Operation

    MGS Series Controller Manual Figure 17. Alarm Response (Dual-Level Alarms) 4.8. Fail Safe Operation The JP1 jumper on the 6-channel controller with dual-level alarm capabilities is used to enable/disable the high-level alarm relay (RL1) to operate in fail-safe mode. Fail-Safe Jumper...
  • Page 29: Muting The Audible Alarm (Key Switch)

    MGS Series Controller Manual 4.9. Muting the Audible Alarm (Key Switch) If service is being carried out on the system or the user does not require a local audible alarm then it can be muted using the key switch. In the default position, the audible alarm is enabled.
  • Page 30: Declaration Of Conformity

    MGS Series Controller Manual ECLARATION OF ONFORMITY The manufacturer of the Bacharach, Inc. products covered by this 621 Hunt Valley Circle declaration: New Kensington, PA 15068 Year conformity is 2012 declared: Product(s): Model(s): MGS Controller The undersigned hereby declares that the above referenced products are in conformity with the provisions of the following standard(s) and is in accordance with the following directive(s).
  • Page 31 MGS Series Controller Manual 6709-9000 Rev 1...
  • Page 32 MGS Series Controller Manual World Headquarters 621 Hunt Valley Circle, New Kensington, Pennsylvania 15068 Phone: 724-334-5000 • Toll Free: 1-800-736-4666 • Fax: 724-334-5001 Website: www.MyBacharach.com • E-mail: help@MyBacharach.com 6709-9000 Rev 1...