3.8 Reinstalling MGS-402 Lid

WARNING: DO NOT leave excess cable inside the gas detector housing. Failure to comply may
result in damage to the product.
CAUTION: When installing the sensor ribbon cable, care must be taken to ensure the proper
orientation of the connector at both ends of the cable. Failure to ensure proper orientation may
result in loss of functionality and/or product damage.
NOTE: To achieve proper seal, the lid screws should be torqued to 15 to 20 lbf in (1.5 to 2.0 Nm.)
Reinstall the rubber gasket. Ensure that it is correctly seated by placing the side with two grooves face down
and the edge with two bumps on the top.
Figure 3-4 -
5. Reconnect the ribbon cable from the sensor to the PCBA as shown.
Figure 3-5 -
WARNING: DO NOT allow the lid / sensor to hang from the ribbon cable. Failure to comply
may result in damage to the product.
12
Rubber Gasket
Ribbon Cable Orientation