Diagnostics & Troubleshooting; Fault Codes - Bacharach MGS-402 User Manual

Gas detection controller for commercial & industrial applications
Table of Contents

Advertisement

MGS-402 User Manual
6. Diagnostics & Troubleshooting

6.1 FAULT CODES

Code
Critical Fault
0001
CHASSIS TEMP
0002
RS485 MSTR BUFR
0004
RS485 SLAVE BUFR Buffer overflow communicating with BMS Use Modbus SLAVE traffic screen to diagnose.
0008
RS485 MSTR CRC
0010
RS485 SLAVE CRC
0040
RS485 SL TMOUT
0200
STUCK KEY ERROR
0400
CONFIG ERROR
1000
SENSOR RESPONSE One or more detectors are not
2000
SUPPLY VOLTS ERR One or more power supply voltages are
4000
CPU ERROR
8000
EEPROM ERROR
24
Possible Causes
Chassis temperature outside the range
of -40 to +50C
Buffer overflow communicating with
detectors
CRC error communicating with detectors
CRC error communicating with BMS
Modbus timeout communicating with BMS Use Modbus SLAVE traffic screen to diagnose.
On or more keys on the keypad are
stuck down
All detectors are disabled or there are
duplicate node addresses
responding to queries
out of range
Microcontroller malfunction
EEPROM malfunction
1100-2570 Rev 1
Remedy
Reduce ambient temperature or check for
power supply malfunction.
Disable all but one channel, use Modbus
MASTER traffic screen to one CH at a time.
Disable all but one channel, use Modbus
MASTER traffic screen to one CH at a time.
Use Modbus SLAVE traffic screen to
diagnose.
Use KEYPAD TEST to determine stuck key,
consult factory.
Enable one or more channels, or check for
duplicate node address assignment.
Disable all but one channel, use Modbus
MASTER traffic screen to test one CH at a
time
Check POWER screen in diagnostic menu,
if SUPPLY OUT is <23.7V check for short or
overload on detector supply feed.
Reset or reboot controller, if fault persist,
consult factory.
Consult factory.