Figure 16. Test Position; Figure 17. Connect Position - Eaton NRX Series User Manual

Low voltage power (air) circuit breakers
Table of Contents

Advertisement

Instructional Book
Effective July 2011
Breaker in cassette
Primary connections not made
Secondary connections made

Figure 16. TEST Position

Figure 17. CONNECT Position

With the circuit breaker sitting solidly on the extension rails in its
WITHDRAWN position, proceed with the following five steps to move
the circuit breaker through its other positions.
Step 1e: Make sure the circuit breaker position indicator, located in
the right lower portion of the circuit breaker, indicates DISCONNECT
(Figure 15).
Step 2e: If the indicator window indicates anything other than
DISCONNECT, use the breaker's on board tool (racking tool) to
get the circuit breaker in the proper levering position. Insert the
levering tool into its compatible front accessible fitting, and rotate it
counterclockwise until DISCONNECT is indicated in the window. An
audible "click" may be heard. This is the levering-in's detent system
engaging, which provides positive feedback when the device is in each
discrete position.
N
otee:
The Detent will engage at each discrete position (Disconnect,
Test, Connect) and requires the user to manually reset the system
before proceeding to the next position.
18
EATON CORPORATION www.eaton.com
MN01301003E
Breaker in cassette
Primary connections made
Secondary connections made
Series NRX Low Voltage Power (Air)
Figure 18. Step 2
Figure 18a. Step 2
Step 3e: Carefully push the circuit breaker into its compartment until it
stops. The extension rails can now be folded up and latched.
Circuit Breakers User Manual
"CLICK" SOUND
DETENT ENGAGED