Commission The Fan Coil Unit; Verify Completion Of Installation - Daikin FWC06B7TV1B Installation Manual

Fan coil units
Table of Contents

Advertisement

Option
Description
BRC7F533F
Remote controller -
wireless (cooling
only)
KRCS01-4
Remote temperature
sensor
DCS302CA51
Central remote
controller
DCS601C51C
Intelligent touch
controller
DCS301BA51
Unified ON/OFF
controller
DST301BA51
Schedule timer
KRP4A(A)53
Wiring adaptor for
electrical appendices
KRP2A52
Wiring adaptor for
electrical appendices
KEK26-1A
Noise filter
KJB212AA
Electrical box with
earth terminal (2
blocks)
KJB311A
Electrical box with
earth terminal (3
blocks)
KJB411A
Electrical box
KRP1H98
Installation box for
adaptor PCB
BRC315D7
Wired remote
controller
EKMV2C09B7
2-way valve
(ON/OFF type)
EKMV3C09B7
3-way valve
(ON/OFF type)
EKRP1C11
Valve control PCB
EKFCMBCB7
Optional PCB for
Modbus connection
Table 4.3: Installation of optional equipment

Commission the fan coil unit

Commission the fan coil unit
FWC
Fan coil units
4PW64525-1B – 2014.03
5
Remark
Not all functions are
Commission the fan coil unit
available for the FWC
5.1.
models.
Installation: refer to
VRV - FXFQ-P.
Installation: direct
connect to indoor
unit, no outdoor unit
After the installation of the unit, first check the following items. Once
connection.
all below checks are fulfilled, the unit must be closed, only then can
Not all functions are
the unit be powered up.
available for the FWC
models.
Installation: direct
connect to indoor
unit, no outdoor unit
connection.
It is not possible to
use AIRNET or
telephone
connection.
Not all functions are
available for the FWC
models.
Installation: direct
connect to indoor
unit, no outdoor unit
connection.
Installation: refer to
FXF(Q).
Connection: refer to
VRV system.
Installation: refer to
FXF(Q).
Connection: refer to
VRV system.
Installation: refer to
VRV - FXFQ-P.
Installation: do not
use the installation
manual delivered
with the option
EKRP1C11, but refer
to the installation
manual of options
EKMV2 and EKMV3
instead.
Commission the fan coil unit
Commission the fan coil unit
Commission the fan coil unit

Verify completion of installation

Danger: electric shock
See
"Precautions for installation" on page
Tick
when checked
The unit is installed properly.
If not installed properly, there may be abnormal noises and
vibrations when starting up the unit.
The unit has been fully insulated.
If not fully insulated, condensate water may drip.
The drainage flows smoothly.
If drainage does not flow smoothly, condensate water may
drip.
The power supply voltage corresponds to the voltage on the
nameplate of the unit.
The wiring and piping connections are correct.
In case of wrong connections, the unit may malfunction or
components may burn out.
The earth wires are connected properly.
The earth terminals have been tightened.
The wiring size is according to specifications.
In case of wrong wiring size, the unit may malfunction or
components may burn out.
The fuses, circuit breakers, or the locally installed protection
devices are of the size and type specified in the chapter
"Prepare the electrical wiring work" on page
None of the fuses or protection devices have been
bypassed.
There are no visible loose connections or damaged
electrical components in the control box or inside the unit.
There are no damaged components or squeezed pipes
inside the unit.
There is no water leakage inside the unit.
If there is water leakage, close the water inlet and water
outlet shut-off valves and call your local DAIKIN dealer.
All air is removed from the circuit.
All options are correctly installed and connected.
The air inlet and outlet of the unit is not obstructed by paper
sheets, cardboard, or any other material.
Table 5.1: Installation completion checklist
Warning
Be sure to provide for adequate measures in order to
prevent that the unit will be used as a shelter by small
animals. Small animals making contact with electrical parts
can cause malfunctions, smoke or fire. Please instruct the
user to keep the area around the unit clean and clear.
2.
4.
Installation manual
10

Advertisement

Table of Contents
loading

Table of Contents