Outdoor Unit Fan Control In Cooling Operation - Daikin ERQ Series Service Manual

Condensing unit three phase
Table of Contents

Advertisement

Basic Control
2.4

Outdoor Unit Fan Control in Cooling Operation

While in cooling operation, if the outdoor temperature is low, this mode provides high-pressure
control using the outdoor unit fan to retain appropriate liquid pressure, thus ensuring refrigerant
circulation rate to be supplied to AHU.
28
Pc < 2.75MPa
Upper limit of outdoor unit
PI control
Lapse of 20 sec.
-1 step on
outdoor unit fan
PI control
Upper limit of fan
revolutions: Step 8
Pc > 3.24MPa
fan revolutions
Step 7
PI control
Hold the
current step on
outdoor unit fan
Lapse of 20 sec.
ESiEN09-06 A
*For fan revolutions in each step,
refer to information on page 107.
+1 step on
outdoor unit fan
Function