Parameters And Codes; Safety Parameters - Riello RX 360 S/PV Modulating Operation

Table of Contents

Advertisement

Available languages

Available languages

4.8.3

Parameters and codes

Most of the functions are controlled by parameters. These pa-
rameters are memorised in the internal memory and pro-
grammed and tested in the factory.
4.8.4

Safety Parameters

No.
Parameter
1
pre-purging time
2
Safety time
3
Flame stabilisation time
4
Ignition attempts
5
Post-purging time
6
Pre-ignition time
7
Ignition time
8
Post-purging speed
9
Maximum speed
14
Minimum limit maximum speed
15
Maximum limit minimum speed
16
Pulses per rotation
17
Frequency of the check of speed
18
Airpress switch
19
APS permanent test
20
Feedback from motor
21
Gas pressure switch
22
Restart
23
Gas valve check
24
Seal valve test
Technical description of the burner
Min.
0.2
0.1
0.1
1
0.2
0.1
0.1
780
780
780
780
1
1
ON
ON
ON
ON
ON
ON
ON
15
GB
It is however possible to change/update the parameter settings
with a BCC card (Burner Chip Card).
Max.
OEM-preset
51
10
25.5
5
51
25.5
25.5
9960
9960
9960
9960
4
2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Value
51
Seconds
3
Seconds
10
Seconds
3
Number
0
Seconds
3
Seconds
3
Seconds
1980
Rotations/min
6000
Rotations/min
4020
Rotations/min
2280
Rotations/min
3
Pulses/rotation
2
Hz
OFF
-
OFF
-
ON
-
OFF
-
OFF
-
OFF
-
OFF
-
20068189
Tab. E

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rx 360 s/pv gpl2006770020104208

Table of Contents