Xytronix Research & Design CONTROL BY WEB XW-111 User Manual page 32

Wireless digital input monitor
Table of Contents

Advertisement

Web Server
The input is considered "On" when the switch connected to the input is closed (connected to the Gnd
terminal).
No remote relay control - The input has no effect on the remote relay.
Remote command equals input - When the input switch is closed, a command is sent to the
remote device to set the relay state to on. When the switch is opened, a command is sent to the
remote device to set the relay state to off.
Remote command opposite of input - When the input switch is closed, a command is sent to
the remote device to set the relay state to off. When the switch is opened, a command is sent to
the remote device to set the relay state to on.
Send on command when input [on, off] (no off command) - When the input switch is [closed,
opened], a command is sent to the remote device to set the relay state to on. When the input
switch is [opened, closed], no commands are sent to the remote device.
Send off command when input [off, on] (no on command) - When the input switch is
[opened, closed], a command is sent to the remote device to set the relay state to off. When the
input switch is [closed, opened], no commands are sent to the remote device.
Send pulse command when input [on, off, changes] - When the input switch is [closed,
opened, changes], a command is sent to the remote device to pulse the relay.
Send toggle command when input [on, off, changes] - When the input switch is [closed,
opened, changes], a command is sent to the remote device to toggle the relay (change the
remote relay to the state opposite of its current state).
If a Remote Relay Option is selected, the following settings are appear:
Hostname / IP Address
Enter the IP address or Host Name of the device on which the remote relay is located. To save energy,
DNS lookups are only performed the first time after the settings are submitted, or after a failure to send a
remote relay command.
TCP Port
Specify the TCP Port. By default this is set to port 80.
Password
Enter the Control Page password (if applicable) of the device on which the remote relay is located.
Relay#
Specify the number of the relay you would like to control on the device. (Note: To control WebRelay's
relay, enter in the number 0.)
Remote Services
The XW-111 can be configured to send messages to other ControlByWeb™ products or servers that are
located at a remote location and running the remote services server software. This field specifies the
action taken due to an input changing state.
Page 32
XW-111™ Wi-Fi Digital Sensor Users Manual
Xytronix Research & Design, Inc.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Control by web xw-111b

Table of Contents