INPUT wIRE SIZE, gROUNdINg ANd OUTPUT wIRINg (continued)
F. Continued
Output wiring sizes:
208/120 VAC
150 Amp breaker
480/277 VAC
70 Amp breaker
480/277 VAC
60 Amp breaker
120 VAC
30 Amp breaker
G. Output neutral to ground bonded during manufacturing of the power conditioner. Output Neutral is
already grounded by the factory.
H. Installation is subject to local codes. Verify with a local electrician inspector.
The unit is constructed using an isolation transformer and is considered to be a "separately derived
system". It should be grounded in accordance with the NFPA 70 article 250.20 "Alternating-Current
Circuits and Systems to be grounded", article 250.20(d) "Separately derived Systems" and article
250.30 "grounding Separately derived Alternating-Current Systems".
*The Output Neutral and ground connection points are common to both wye outputs (208/120
vAC & 480/277 vAC). Therefore, it is considered a single, separately derived, power source and
should be wired accordingly.
#14 AWG to #3/0 AWG
#14 AWG to #3/0 AWG
#14 AWG to #3/0 AWG
#14 AWG to #2 AWG
9
1402-001