160K(i) 60 Hz Power Conditioner | Owners Manual
14

BYPASS SWITCH

**** CAUTION ****
Prior to switching from one position to another- turn off the AC input breaker.
The manual bypass switch is a break before make switch located on the Series 700 AV/T-S. The manual
bypass switch is used to bypass all power electronics in case of failure.
This is a no load switch and MUST only be operated when the unit is OFF. The bypass switch should be
in the "NORMAL" position unless a problem occurs with the system. If a problem occurs, turn OFF the
main AC circuit breaker and turn the bypass switch to the "BYPASS" position. Re-energize the system
by turning on the AC circuit breaker and contact the Customer Support Department for repairs.
NORMAL MODE
With the switch in the normal position, the Series 700 AV/T-S will provide clean and regulated power to
the critical loads. The Series 700 AV/T-S should have the switch in the normal position unless a failure
has occurred.
BYPASS MODE
With the switch in the bypass position, the Series 700 AV/T-S will provide clean power to the critical loads.
In the bypass position, the unit will not regulate the incoming voltage. The Series 700 AV/T-S should be
placed in the bypass position when a failure of the system has occurred. This provides the user with some
protection until a service technician arrives.
REMOTE EMERGENCY POWER OFF (REPO) OPTION
The REPO is operated by a remote push button that when depressed will shunt trip the Series 700 AV/T-S
input breaker and disable the unit. This option may be added to units in the field.
Contact the Customer Support Department if you wish to add this option.