PRELImINARY INSTALLATION (continued)
INPUT AND OUTPUT BREAKER SIZE
OUTPUT KVA
INPUT
CONTINUOUS
BREAKER SIZE
75 kVA
300A @ 208V
250A @ 240V
150A @ 480V
100A @ 600V
WEIGHTS, BTU AND DIMENSIONS
OUTPUT KVA
WEIGHT
75 kVA
2,194 lbs
995.18 kg
* Stated BTU's / Hr is at 75kVA rated load, 100% duty cycle. Operational BTU's / Hr is typically at
50% of rated load. Input over current protection provided by others.
To reduce the risk of fire, use only on circuits provided with ampere
branch circuit protection as noted in the table above, in
accordance with the National Electric Code, ANSI/NFPA 70.
If unit is provide with no output circuit breaker option, output over-current protection
and a disconnect device (circuit breaker) shall be provided by others.
OUTPUT BREAKER SIZE
150A, 3P @ 208V Accelerator
70A, 3P @ 480V BL Generator
60A, 3P @ 480V OBI
30A, 1P @ 120V BL Computers
OPERATIONAL
MAXIMUM
BTU/HR
BTU/HR
TYPICAL
5,115*
10,230
**** CAUTION ****
MAX OUTPUT CURRENT
208/120V 125A Accelerator
480/277V 70A BL Generator
480/277V 55A OBI
120V 25A BL Computers
DIMENSIONS
34.5" w x 35.875" d x 76" h
87.63 cm x 91.12 cm x 193.04 cm
7
1402-001