Infinite Transtector 700 AV/T-S Series Owner's Manual page 13

160ki power conditioner with voltage regulation 60 hz, quad output power conditioner for novalis tx with exactrac and obi options, front access design
Table of Contents

Advertisement

INSTALLATION (continued)
INPUT AND OUTPUT CONNECTIONS
1. Input connections are made directly to the unit's 3 pole main input circuit breaker and input lug provided.
Note the bottom access wire run route illustrated below.
2. Output connections are made directly to the output breaker(s) and output neutral and ground lugs
provided. The load current is not to exceed 80% of the output breaker(s) rating, and not to exceed
the rated total current.
OUTPUT METERS
OUTPUT TERMINATIONS
COPPER BUS
OUT OF RANGE &
MONITOR ALERT
LIGHTS
BYPASS SWITCH
150A 208V
OUTPUT
BREAKER
DETAIL A
70A 480V
OUTPUT
SCALE 1 : 2
BREAKER
FRONT VIEW
A
INPUT OUT OF RANGE
ALERT
A
B
C
OUTPUT CONDITIONED POWER
SEPERATION PLATE
BOTTOM ACCESS WIRE RUN ROUTE
30A 120V
OUTPUT
BREAKER
60A 480V OUTPUT BREAKER
INPUT GROUND LUG (1) TA 250
WIRE RANGE: 6 AWG - 250 MCM
INPUT CIRCUIT BREAKER
(CUSTOMER'S INPUT CONNECTS
TO TOP)
13
1402-001

Advertisement