AM Series Pool Heater User Manual
SECTION 5: INSTALLATION – PIPING
5.9.2 Bypass Flow Piping Method
A bypass flow system is recommended under one or more of the following conditions:
•
If the total system flow is greater than the amount required by the indirect heat exchanger.
•
If pool or spa water system exceeds 95°F in temperature, a bypass flow configuration is
used to cool down the return flow in order to prevent tripping the high limit switch and to
prevent water with temperatures over 115°F from entering the pool or spa system.
•
Multiple unit installations.
An example of the configuration and necessary components for a bypass flow system are shown
in Figure 5-5b.
FLOW SWITCH
FILTER
PUMP
FROM
POOL /
SKIMMER
OMM-0111_B: • GF-146-P • 10/29/2019
EXCHANGER
BYPASS PIPING
TO POOL
Figure 5-5b: Bypass Flow Piping Method
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
BOILER
HEAT
CHLORINATOR
(DOWNSTREAM)
HIGH TEMP.
SWITCH
Page 30 of 47