SECTION 3: INSTALLATION - SITE
SECTION 3: INSTALLATION – SITE

3.1 Choosing the Installation Location

This section describes the general installation considerations for the AM Series Pool Heaters.
WARNING!
Provisions for combustion air and ventilation of the boiler room are always required, regardless
whether the combustion air is taken from the outside (Direct Vent, sealed combustion) or inside
(room air for combustion). Insufficient ventilation of the boiler room can lead to high air
temperatures. Make sure that intake and exhaust openings are sufficiently sized and no
reduction or closure of openings takes place. If these are not provided, do not operate the
boiler.
WARNING!
LIQUEFIED PETROLEUM (L.P.) PROPANE GAS-FIRED BOILER LOCATION REQUIRES
SPECIAL ATTENTION: 1994 UNIFORM MECHANICAL CODE, section 304.6: "LPG
Appliances. Liquefied petroleum gas-burning appliances shall not be installed in a pit,
basement or similar location where heavier-than-air-gas might collect. Appliances so fueled
shall not be installed in an above grade under-floor space or basement unless such location is
provided with an approved means for removal of unburned gas."
This appliance is not designed for direct outdoor installation. If installed outside of the structure,
it must be sheltered so it is protected from rain, wind, sun and frost. NEVER place this appliance
in a location that would subject it to temperatures at or near freezing or excessively high
temperature. Failure to properly locate this unit can result in premature failure.
The boiler must NOT be installed on carpeting.
This appliance must be installed in a location so that any water leaking from the unit or piping
connections or relief valve openings will not cause damage to the area surrounding the unit or
any lower floors in the structure. When such locations cannot be avoided, it is recommended that
a suitable drain pan, adequately drained, be installed under the boiler. The pan must not restrict
combustion air flow.
When installed in a room with thin flooring, resonating noises may occur. Install noise reducing
parts if required.
Do not allow excessive dust to collect on the appliance.
WARNING!
Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or
any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch.
Do not use any phone in the building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas
supplier's instructions.
If you cannot contact your gas supplier, call the fire department.