Specifications; Boiler - Burner Modules, Efficiency, Flow Rate, And Water Connections; Boiler - Exhaust Manifold, Condensate Trap, And Condensate Neutralizer; Am Pool Heater Supply And Return Piping Dimensions - Watts Aerco AM Series Operation & Maintenance Manual

Natural gas and propane gas modulating condensing pool heating system
Table of Contents

Advertisement

AM Series Pool Heater User Manual
CHAPTER 2: FUNCTION & SPECIFICATIONS

2.2 Specifications

2.2.1 Boiler - Burner Modules, Efficiency, Flow Rate, and Water Connections

Each AM Series pool heating system includes a boiler featuring from 2 to 4 thermal modules,
depending on model, performing total turn down ratios without loss of combustion efficiency as
shown in the table below. Each thermal module's premix burner is a metal fiber mesh covering a
stainless steel head, with spark ignition and flame rectification. All burner materials exposed to
the combustion zone are of stainless steel construction. There are no moving parts within the
burner itself. The burners produce <20 ppm of NOx corrected to 3% excess oxygen. A modulating
gas valve, and variable speed fan, meter the natural gas and air input, respectively.
Each module has a dedicated isolation valve on the inlet side of the module on the rear of the
unit. The table below shows the pool flow rates for each model, as well as the water connection
sizes.
AM Series Pool Heating System General Specifications
Model
# Modules
AM 399P
2
AM 500P
2
AM 750P
3
AM 1000P
4

2.2.2 Boiler - Exhaust Manifold, Condensate Trap, and Condensate Neutralizer

NOTE:
Refer to Section 5.6 of this document for detailed information concerning the condensate trap
and neutralizer tank installation and maintenance.

2.2.3 AM Pool Heater Supply and Return Piping Dimensions

Connections and dimensions for AM Series pool heaters are shown in Figure 2-3a and 2-3b
over the following pages.
OMM-0111_B: • GF-146-P • 10/29/2019
Turndown
Pool Water
Ratio
Maximum Flowrate
8:1
127 GPM
10:1
127 GPM
15:1
222 GPM
20:1
222 GPM
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Connection Pool
Side
3 inches NPT
3 inches NPT
3 inches Flg ANSI 150
3 inches Flg ANSI 150
Page 10 of 47