AM Series Pool Heater User Manual
SECTION 5: INSTALLATION – PIPING
5.5 Safety Relief Valve
AM units come equipped with a safety relief valve on each factory installed module. Boilers are
supplied with 50 PSI pressure relief valves. If a higher or lower rated PRV is required it must be
field supplied and installed.
Pipe the discharge of the safety relief valve(s) (Figure 5-1) to a suitable drain to prevent injury in
the event of pressure relief. Each relief valve must have its own discharge piping, be piped to
within 12" of the ground, and not be combined with any other piping all the way to the point of
discharge into a drain. Provide piping that is the same size as the safety relief valve outlet.
SAFETY RELIEF
VALVE & T&P GAUGE
SAFETY RELIEF
VALVE & T&P GAUGE
HOT WATER SUPPLY
OUTLET (Factory Connected)
SAFETY RELIEF
VALVE & T&P GAUGE
WATER RETURN
INLET (Factory Connected)
SAFETY RELIEF
VALVE & T&P GAUGE
Figure 5-1: Discharge Piping for Boiler Relief Valves (AM 1000 Boiler Shown)
OMM-0111_B: • GF-146-P • 10/29/2019
#1
#2
#3
#4
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
FIELD INSTALLED:
RELIEF VALVE DISCHARGE
PIPING (one for each valve
and piped to within 12" of
ground)
Page 26 of 47