Sine Output Filter Data - ABB ACS880-37 Hardware Manual

Abb industrial drives (45...400 kw, 60...450 hp)
Hide thumbs Also See for ACS880-37:
Table of Contents

Advertisement

*
Natural convection

Sine output filter data

Sine output filters are available as option +E206. The table below shows the types and
technical data of the filters and filter cubicles used in the drive.
Drive type
ACS880-37-...
Qty
U
= 400 V
N
0105A-3
1
0145A-3
1
0169A-3
1
0206A-3
1
0293A-3
1
0363A-3
1
0442A-3
1
0505A-3
1
0585A-3
1
0650A-3
1
U
= 500 V
N
0101A-5
1
0124A-5
1
0156A-5
1
0180A-5
1
0260A-5
1
0302A-5
1
0361A-5
1
0414A-5
1
0460A-5
1
0503A-5
1
U
= 690 V
N
0174A-7
1
0210A-7
1
0271A-7
1
0330A-7
1
0370A-7
1
0430A-7
1
*
Natural convection
I
Continuous rms output current. No overload capability at 40 °C (104 °F)
N
Sine filter(s) used
Type
B84143V0130S230
B84143V0162S229
B84143V0162S229
B84143V0230S229
B84143V0390S229
B84143V0390S229
B84143V0390S229
NSIN0900-6
NSIN0900-6
NSIN0900-6
B84143V0130S230
B84143V0130S230
B84143V0162S229
B84143V0162S229
B84143V0230S229
B84143V0390S229
B84143V0390S229
B84143V0390S229
NSIN0900-6
NSIN0900-6
B84143V0207S230
B84143V0207S230
B84143V0207S230
NSIN0485-6
NSIN0485-6
NSIN0485-6
Cooling data
I
N
Heat dissipation
A
kW
105
0.63
145
0.55
169
0.55
206
0.90
264
1.57
327
1.57
398
1.57
455
2.89
527
3.35
585
3.73
101
0.63
124
0.63
156
0.55
180
0.55
234
0.90
272
1.57
325
1.57
373
1.557
414
3.16
453
3.46
157
0.93
189
0.93
244
0.93
297
2.0
333
2.2
387
2.6
Technical data 217
Air flow
3
3
m
/h (ft
/min)
*
*
*
*
*
*
*
2000 (1177)
2000 (1177)
2000 (1177)
*
*
*
*
*
*
*
*
2000 (1177)
2000 (1177)
*
*
*
700 (412)
700 (412)
700 (412)

Advertisement

Table of Contents
loading