Single package, electric heat 3 thru 5 tons - 208/230v - 3 phase
Hide thumbs Also See for PCE4 Series:

Advertisement

INSTALLATION MANUAL
SINGLE PACKAGE
AIR CONDITIONER / ELECTRIC HEAT
MODELS: PCE4 SERIES
3 THRU 5 TONS - 208/230V - 3 PHASE
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
MODEL NUMBER NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
AIRFLOW PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Unit 4 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Bottom Duct Dimensions (Inches) . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rear Duct Dimensions (Inches) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Single Point Kit Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical Data for 208-3-60 Multi Source Power . . . . . . . . . . . . . . . . 8
Electrical Data for 230-3-60 Multi Source Power . . . . . . . . . . . . . . . . 9
SECTION I: GENERAL INFORMATION
PCE units are factory assembled air conditioners designed for outdoor
installation on a roof top or a slab. Field-installed electric heater acces-
sories are available to provide electric heat.
The units are completely assembled on rigid, removable base rails. All
piping, refrigerant charge, and electrical wiring is factory installed and
tested. The units require only electric power and duct connections at
the point of installation.
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
Johnson Controls Ducted Systems
LIST OF SECTIONS
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
TYPICAL WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
LIST OF FIGURES
Typical Field Power Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Single Point Wiring Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Measuring External Static Pressure . . . . . . . . . . . . . . . . . . . . . . . . . 14
Connection Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Ladder Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
R-410A Quick Reference Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
LIST OF TABLES
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Airflow Performance - Side Duct Application . . . . . . . . . . . . . . . . . . 11
Airflow Performance - Bottom Duct Application . . . . . . . . . . . . . . . . 12
Electric Heat Minimum Supply Air . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electric Heat Multipliers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Additional Static Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Thermostat Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance
can cause injury or property damage. Failure to carefully read and
follow all instructions in this manual can result in furnace mal-
function, death, personal injury and/or property damage. Only a
qualified contractor, installer or service agency should install this
product.
This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
® ®
WARNING
!
CAUTION
!
5538117-UIM-B-0319

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PCE4 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Johnson Controls PCE4 Series

  • Page 1: Table Of Contents

    SINGLE PACKAGE ® ® AIR CONDITIONER / ELECTRIC HEAT MODELS: PCE4 SERIES 3 THRU 5 TONS – 208/230V - 3 PHASE LIST OF SECTIONS GENERAL INFORMATION ....... . 1 OPERATION .
  • Page 2: Model Number Nomenclature

    Air Conditioning Contractors of America (manual J). 2. Local plumbing and waste water codes and other applicable local codes. TABLE 1: Unit Limitations Unit Limitations Model Unit Voltage Applied Voltage Outdoor DB Temp Max (°F) PCE4A36 208/230-3-60 PCE4B48 208/230-3-60 PCE4B60 208/230-3-60 Johnson Controls Ducted Systems...
  • Page 3: Component Location

    6. Maintain level tolerance to 1/8” across the entire width and length of unit. rails are provided for this purpose. CLEARANCES All units require certain clearances for proper operation and service. Refer to Table 4 for the clearances required for construction, servicing and proper unit operation. Johnson Controls Ducted Systems...
  • Page 4: Unit 4 Point Load Weight

    PCE4B60 51-1/4 45-3/4 COIL GUARD HIGH VOLTAGE CONNECTION 7/8” HIGH VOLTAGE CONNECTION 1-3/32” HEAT SECTION COMPRESSOR ACCESS PANEL ACCESS PANEL CONDENSATE DRAIN BLOWER LOW VOLTAGE CONNECTION ACCESS CONTROL ACCESS PANEL PANEL A0379-001 FIGURE 3: Unit Dimensions Johnson Controls Ducted Systems...
  • Page 5: Bottom Duct Dimensions (Inches)

    It is the responsibility of the installer to secure a filter in the return air B48, B60 13.6 ductwork or utilize the filter rack. FIGURE 5: Rear Duct Dimensions (Inches) A filter rack kit is included with all three phase units. Johnson Controls Ducted Systems...
  • Page 6: Typical Field Control Wiring Diagram For Air Conditioner Models

    This service disconnect orientation change is required by conditions are indicated on the unit Rating Plate and Table 1. UL1995, Article 26.19 (in reference to all circuit breakers). Johnson Controls Ducted Systems...
  • Page 7: Single Point Kit Numbers

    6HK16502025 S1-2SPWK035 N/A* 6HK06501025 S1-2SPWK032 6HK06501525 S1-2SPWK034 PCE4B60 230-3-60 6HK06501825 S1-2SPWK034 6HK16502025 S1-2SPWK035 N/A* 6HK16502525 S1-2SPWK035 N/A* NOTES: * The 208/230 volt 20kW and 25kW heater kits include circuit breakers. FIGURE 8: Single Point Wiring Kit Johnson Controls Ducted Systems...
  • Page 8: Electrical Data For 208/230-3-60 Single Source Power

    6HK16502025 14.4 40.0 28.7 25.0 25.0 6HK16502525 18.0 50.0 28.7 31.3 31.3 1. MCA = Minimum Circuit Ampacity. 2. MOP = Maximum Over Current Protection device; must be HACR type circuit breaker or time delay fuse. Johnson Controls Ducted Systems...
  • Page 9: Electrical Data For 230-3-60 Multi Source Power

    6HK16502025 17.6 44.3 28.7 27.7 27.7 6HK16502525 22.0 55.3 28.7 34.6 34.6 1. MCA = Minimum Circuit Ampacity. 2. MOP = Maximum Over Current Protection device; must be HACR type circuit breaker or time delay fuse. Johnson Controls Ducted Systems...
  • Page 10: Physical Data

    Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through dispos- Quantity - Size able filters. For internal filter use, a filter rack kit is included with all three phase models. Consult the instructions supplied with that kit for replacement filter sizes. Filter sizes: A=20x20, B=20x30. Johnson Controls Ducted Systems...
  • Page 11: Airflow Performance

    4. Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases. 5. Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards. Johnson Controls Ducted Systems...
  • Page 12: Airflow Performance - Bottom Duct Application

    TABLE 13: Electric Heat Multipliers Voltage kW Capacity Multipliers Nominal Applied 0.75 0.92 1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat capacity for heaters applied at lower voltages. Johnson Controls Ducted Systems...
  • Page 13: Operation

    “W” signal. When the 24V signal is removed from the electric heat sequencer, the heating elements will turn off. The indoor blower will continue to run for 60 seconds after the call for heat is removed. Johnson Controls Ducted Systems...
  • Page 14: Maintenance

    If water is used to clean the coil, be sure that the power to the unit is shut off prior to cleaning. NOTICE DO NOT use a pressure washer as coil fin damage will occur. Johnson Controls Ducted Systems...
  • Page 15: Typical Wiring Diagrams

    APPROX. 400 CFM/TON IN COOLING. 7. IF ELECTRIC HEAT IS INSTALLED, SELECT A HEATING BLOWER SPEED THAT DELIVERS SUFFICIENT AIRFLOW TO SUIT THE WATTAGE OF ELECTRIC HEAT INSTALLED. SEE TABLE IN INSTALLATION MANUAL. 5146413-UWD-B-0915 FIGURE 10: Connection Wiring Diagram Johnson Controls Ducted Systems...
  • Page 16: Ladder Wiring Diagram

    7. IF ELECTRIC HEAT IS INSTALLED, SELECT A HEATING BLOWER SPEED THAT MOVE BLACK WIRES FROM THE 230 TO THE 208 VOLT TAP ON THE TRANSFORMER. DELIVERS SUFFICIENT AIRFLOW TO SUIT THE WATTAGE OF ELECTRIC HEAT INSTALLED. SEE TABLE IN INSTALLATION MANUAL. FIGURE 11: Ladder Wiring Diagram Johnson Controls Ducted Systems...
  • Page 17: R-410A Quick Reference Guide

    Never open system to atmosphere when under a vacuum. If system must be opened for service, evacuate system then break the vacuum with dry nitrogen and replace all filter driers. FIGURE 12: R-410A Quick Reference Guide Johnson Controls Ducted Systems...
  • Page 18 5538117-UIM-B-0319 NOTES Johnson Controls Ducted Systems...
  • Page 19: Start Up Sheet

    Supply air dry bulb temperature Outside air dry bulb temperature Return static (inches of water column) Return air dry bulb temperature Return air wet bulb temperature Total external static pressure Temperature drop Supply air wet bulb temperature Johnson Controls Ducted Systems...
  • Page 20 Explain the importance of regular filter replacement and equipment maintenance Comments and Additional Job Details Subject to change without notice. Published in U.S.A. 5538117-UIM-B-0319 Copyright © 2019 by Johnson Controls. All rights reserved. Supersedes: 5538117-UIM-A-0918 York International Corp. 5005 York Drive...