Johnson Controls PHP024 Installation Manual

Johnson Controls PHP024 Installation Manual

R-22, 13 seer

Advertisement

Quick Links

R-22, 13 SEER
PHP024-060
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Unit Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
(Manufactured Housing) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Supply and Return Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . 6
The Return - Air Grille Boxes . . . . . . . . . . . . . . . . . . . . . . 6
Wye Insulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Discharge Duct Installation . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installing Of Duct To Unit (Residential) . . . . . . . . . . . . . . . . . . 9
Installing Drain Tube And Connection . . . . . . . . . . . . . . . . . . . 9
1 Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 Demand Defrost Selection . . . . . . . . . . . . . . . . . . . . . . . 12
5 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6 Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1 Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Air Discharge Clearance . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Unit 4 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . 4
4 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5 Return Air Box and Grille . . . . . . . . . . . . . . . . . . . . . . . . . 6
6 Wye Installation (Outlet) . . . . . . . . . . . . . . . . . . . . . . . . . . 7
7 Wye Installation (Inlet and Outlet) . . . . . . . . . . . . . . . . . . 8

General

Model PHP units are factory assembled heat pump designed to
be installed along side the home or building. Field-installed
electric heater accessories are available to provide
supplemental electric heat.
The units are completely assembled on rigid base rails. All
piping, refrigerant charge, and electrical wiring is factory
installed and tested. The units require only electric power and
duct connections at the point of installation.
The electric heaters have nickel-chrome resistance wire
elements and utilize single point power connection.
Safety Considerations
This is a safety alert symbol
labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention to the signal words
DANGER, WARNING or CAUTION.

TABLE OF CONTENTS

LIST OF TABLES
LIST OF FIGURES
. When you see this symbol on
Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Power And Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Power Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Wall Thermostat Installation . . . . . . . . . . . . . . . . . . . . . . . . . 10
Pre-start Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
System Startup, Check-out . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Other Features Incorporated In The Control . . . . . . . . . . . . . 11
Anti-Short Cycle time Delay . . . . . . . . . . . . . . . . . . . . . . . 11
Safety Lock-Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Normal Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7 Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8 Additional Static Resistance . . . . . . . . . . . . . . . . . . . . . . 15
9 Electric Heat Minimum Supply Air . . . . . . . . . . . . . . . . . 17
10 Indoor Blower Specifications . . . . . . . . . . . . . . . . . . . . . . 17
11 Electric Heat Multipliers . . . . . . . . . . . . . . . . . . . . . . . . . 17
8 Duct Connector (With Damper) . . . . . . . . . . . . . . . . . . . . 8
9 Duct Connector (No Damper) . . . . . . . . . . . . . . . . . . . . . 8
10 Unit Component Location . . . . . . . . . . . . . . . . . . . . . . . 10
11 Thermostat Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
12 Switch Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
13 Defrost Operation Curves . . . . . . . . . . . . . . . . . . . . . . . 12
DANGER indicates an imminently hazardous situation, which,
if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which,
if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if
not avoided may result in minor or moderate injury. It is also
used to alert against unsafe practices and hazards involving
only property damage.
Improper installation may create a condition where the
operation of the product could cause personal injury or
property damage. Improper installation, adjustment,
alteration, service or maintenance can cause injury or
property damage. Refer to this manual for assistance or
for additional information, consult a qualified contractor,
installer or service agency.
SO 9001
Certified Quality
Management System
166349-BIM-E-1008

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PHP024 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Johnson Controls PHP024

  • Page 1: Table Of Contents

    R-22, 13 SEER PHP024-060 SO 9001 Certified Quality 2-5 Ton Management System TABLE OF CONTENTS General ......... . 1 Service Access .
  • Page 2: Installation

    Local plumbing and waste water codes and other applicable local codes. These units must be installed in accordance with the following national and local safety codes. Refer to Table 6 for unit physical data and to Table 5 for electrical data. Johnson Controls Unitary Products...
  • Page 3: Unit Location

    Site – Select a solid level position, preferably on a concrete possible to the proposed return grille location. Unit may be slab, slightly above grade level and parallel to the home. positioned to draw air from underneath structure. Johnson Controls Unitary Products...
  • Page 4: Site Preparation

    Front Figure 3: Unit 4 Point Load Weight Size Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.) (Tons) Shipping Operating 21.75 (2.0) 21.75 (2.5) 23.5 (3.0) 23.5 (3.5) 28.75 16.25 (4.0) 28.75 16.25 (5.0) Johnson Controls Unitary Products...
  • Page 5: Unit Dimensions

    10 5/16 28 7/8 2 3/4 (3.5) 32 13/16 34 11/16 57 9/16 11 9/16 10 5/16 28 7/8 2 3/4 (4.0) 32 13/16 34 11/16 57 9/16 11 9/16 10 5/16 28 7/8 2 3/4 (5.0) Johnson Controls Unitary Products...
  • Page 6: Installing Of Duct To Unit (Manufactured Housing)

    Any duct used should be covered with insulation pull the flex duct up through the hole and fasten to the having a minimum R-value of 4.0 or in accordance with any return box. local codes or standards regarding duct material. Insulation Johnson Controls Unitary Products...
  • Page 7: Wye Insulation

    Greater Efficiency and 8” static pressure Performance of Unit. ” Inlet Outlet Separate Accessories Available: Flange Flange 7336A5811 WYE (12” Dia.) 7336-7121 Duct Connector and Filter Package 7336-5801 Duct Connector Figure 6: Wye Installation (Outlet) Johnson Controls Unitary Products...
  • Page 8: Discharge Duct Installation

    Factory Installed Hinged, Heating Damper Blocks Flow of Warm Air Into Condensing Unit During Heating Season. Duct Connector (No Damper) Duct Connector (With Damper) Figure 9: Duct Connector (No Damper) Figure 8: Duct Connector (With Damper) Johnson Controls Unitary Products...
  • Page 9: Installing Of Duct To Unit (Residential)

    Failure to do so will control box through the bottom knockout opening in the result in condensate water overflowing into the unit’s casing. (The two top knockouts are used when installing an interior. auxiliary heater.) Johnson Controls Unitary Products...
  • Page 10: Control Wiring

    Avoid locations close to radiators, warm air registers, or in the direct path of heat or cold air from them. Make sure that there are no pipes or ductwork in that part of the wall chosen for thermostat location. Johnson Controls Unitary Products...
  • Page 11: Pre-Start Procedure

    The unit will start up after the 5 Set the wall thermostat system switch to COOL and the minute delay, mentioned above. temperature selection lever below the room temperature. The heat pump should be running in the cooling mode. Johnson Controls Unitary Products...
  • Page 12: Demand Defrost Selection

    Table 4: Demand Defrost Selection Unit Pin Position DEMAND PHP 024, 030, 042 DEFROST SELECTION PHP 036, 048, 060 JUMPER (JUMPER IS SHOWN IN POSITION W1/66 PRESSURE VALVE SWITCH Figure 14: Demand Defrost “Curve” Selection Jumper Johnson Controls Unitary Products...
  • Page 13: Ton

    7.2/9.6 34.5/39.8 84.6/91.3 100/100 (5.0) 2PH08511506 10.8/14.3 51.7/59.7 106.2/116.1 110/125 208/230-3-60 16.6 120.0 26.0 None 30.3 460-3-60 60.0 13.0 None 15.2 1. Minimum Circuit Ampacity. 2. Dual Element, Time Delay Type. 3. HACR type per NEC. Johnson Controls Unitary Products...
  • Page 14: Physical Data

    11 x 10 11 x 10 Type Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Drive type Direct Direct Direct Direct Direct Direct No. speeds Number of motors Motor HP each 1100 1100 1100 1100 1100 1100 Frame size Johnson Controls Unitary Products...
  • Page 15: Airflow Performance

    0.12 0.10 0.10 0.11 0.13 (3.0) 1000 0.12 0.12 0.12 0.13 0.15 1100 0.13 0.13 0.13 0.14 0.17 1200 0.15 0.15 0.15 0.16 0.19 1300 0.17 0.17 0.17 0.18 0.21 1400 0.19 0.19 0.19 0.20 0.23 Johnson Controls Unitary Products...
  • Page 16 1700 0.31 0.31 0.31 0.32 0.35 1800 0.33 0.33 0.33 0.34 0.37 1900 0.35 0.35 0.35 0.36 0.39 2000 0.37 0.37 0.37 0.38 0.41 2100 0.39 0.39 0.39 0.40 0.43 2200 0.41 0.41 0.41 0.42 0.45 Johnson Controls Unitary Products...
  • Page 17: Maintenance

    FILTERS - Inspect once a month. Replace Disposable or clean are not damaged. Permanent Type as necessary. DO NOT replace Permanent Do not permit the hot condenser air discharge to be Type with Disposable. obstructed by overhanging structures or shrubs. Johnson Controls Unitary Products...
  • Page 18: Typical Wiring Diagrams

    166349-BIM-E-1008 Typical Wiring Diagrams PHP024-060 Typical Heat Pump 208/230-1-60 volt Wiring Diagram Johnson Controls Unitary Products...
  • Page 19 166349-BIM-E-1008 PHP036, 048 and 060 Typical Heat Pump 208/230-3-60 volt Wiring Diagram Johnson Controls Unitary Products...
  • Page 20 PHP060 Typical Heat Pump 460-3-60 volt Wiring Diagram Subject to change without notice. Printed in U.S.A. 166349-BIM-E-1008 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 166349-BIM-D-1206 Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069...

This manual is also suitable for:

Php060Php030Php036Php042Php048

Table of Contents