Single package air conditioner/electric heat 2 ton to 5 ton - 208/230 v - single-phase

Advertisement

Quick Links

INSTALLATION MANUAL
Single Package
Air Conditioner/Electric Heat
Models: PCE6 Series
2 ton to 5 ton - 208/230 V - Single-Phase
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Model number nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Airflow performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Component location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Unit four-point load weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Bottom duct dimensions (in.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rear duct dimensions (in.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Typical field power wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Unit limitations - PCE6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Application limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Weights and dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Electrical data for 208-1-60 multi source power . . . . . . . . . . . . . . . . . 7
Electrical data for 230-1-60 multi source power . . . . . . . . . . . . . . . . . 8
Single-point wiring kit part numbers . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Section I: General information

PCE units are factory assembled air conditioners designed for outdoor
installation on a rooftop or a slab. Field installed electric heater acces-
sories are available to provide electric heat.
The units are completely assembled on rigid, removable base rails. All
piping, refrigerant charge, and electrical wiring is factory installed and
tested. The units require only electric power and duct connections at
the point of installation.

Section II: Safety

This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
Johnson Controls Ducted Systems
List of sections
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Typical wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Start-up sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
List of figures
Single-point wiring kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Indoor blower control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Measuring external static pressure . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Connection wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Ladder wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
R-410A quick reference guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
List of tables
Electric heat blower off delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Physical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Airflow performance - side duct application . . . . . . . . . . . . . . . . . . . 11
Electric heat performance data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Additional static resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Delay profile descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Thermostat signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Minimum blower speed for electric heat . . . . . . . . . . . . . . . . . . . . . . 14
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service, or maintenance
can cause injury or property damage. Failure to carefully read and
follow all instructions in this manual can result in furnace mal-
function, death, personal injury, and/or property damage. Only a
qualified contractor, installer, or service agency should install this
product.
This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes,
including but not limited to building, electrical, and mechanical codes.
Assembled at a facility with
an ISO 9001:2015-certified
®
Quality Management
System
WARNING
!
CAUTION
!
6310638-UIM-B-0823

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PCE6 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Johnson Controls PCE6 Series

  • Page 1: Table Of Contents

    INSTALLATION MANUAL Single Package Air Conditioner/Electric Heat Models: PCE6 Series Assembled at a facility with 2 ton to 5 ton - 208/230 V - Single-Phase an ISO 9001:2015-certified ® Quality Management System List of sections General information ........1 Operation .
  • Page 2: Section Iii: Model Number Nomenclature

    Maximum All Models 208/230-1-60 Table 2: Application limitations Air temperature at outdoor coil (°F) Air temperature at indoor coil (°F) Packaged equipment series Minimum Maximum Minimum Maximum DB cool DB cool WB cool WB cool PCE6 Johnson Controls Ducted Systems...
  • Page 3: Component Location

    The outdoor coils should be protected from rigging cable damage air discharge outlet. with plywood or other suitable material. Clearances All units require certain clearances for proper operation and service. See Table 5 for the clearances required for construction, servicing, and proper unit operation. Johnson Controls Ducted Systems...
  • Page 4: Unit Four-Point Load Weight

    CONTROL / HEAT PANEL ACCESS PANEL A0379-003 Figure 3: Unit dimensions Table 4: Unit dimensions Dimensions (in.) Model PCE6A24 51 1/4 35 3/4 PCE6A36 51 1/4 35 3/4 PCE6B48 51 1/4 45 3/4 PCE6B60 51 1/4 45 3/4 Johnson Controls Ducted Systems...
  • Page 5: Bottom Duct Dimensions (In.)

    Check filters monthly. This is especially important because the unit can Model be used for both heating and cooling. 24, 36 48, 60 13.6 Figure 5: Rear duct dimensions (in.) Johnson Controls Ducted Systems...
  • Page 6: Typical Field Control Wiring Diagram For Air Conditioner Models

    This service disconnect orientation change is required by sor terminals during starting and running conditions. UL 1995, Article 26.19 (in reference to all circuit breakers). Note: Provide the wiring entering the cabinet with mechanical strain relief. Johnson Controls Ducted Systems...
  • Page 7: Electrical Data For 208/230-1-60 Single Source Power

    6HK(0,1)6501006 34.7 28.4 43.3 PCE6B48 17.1 109.0 26.6 1.7 6HK16501506 10.8 52.0 28.4 21.7 43.3 6HK16502006 14.4 69.3 28.4 43.3 43.3 6HK26501506 10.8 52.0 28.4 65.0 6HK26502006 14.4 69.3 28.4 86.7 Table continued on next page Johnson Controls Ducted Systems...
  • Page 8: Electrical Data For 230-1-60 Multi Source Power

    57.5 38.0 71.9 6HK26502006 17.6 76.7 38.0 95.8 6HK26502506 22.0 95.8 38.0 119.8 1. MCA = Minimum Circuit Ampacity. 2. Maximum Overcurrent Protection per standard UL 1995. 3. Fuse or HACR circuit breaker is field installed. Johnson Controls Ducted Systems...
  • Page 9: Single-Point Wiring Kit Part Numbers

    Up to 10 PCE6A36 S1-2SPWK002 Up to 15 PCE6B48 S1-2SPWK003 Up to 20 PCE6B60 S1-2SPWK005 Up to 20 Table 10: Electric heat blower off delay Model ID Blower off delay in seconds PCE6A24 PCE6A36 PCE6B48 PCE6B60 Johnson Controls Ducted Systems...
  • Page 10: Physical Data

    For internal filter use, a filter rack kit is available. Refer to the instructions Quantity - size supplied with the kit for replacement filter sizes. Filter sizes: A = 20 in. x 20 in., B = 20 in. x 30 Johnson Controls Ducted Systems...
  • Page 11: Section V: Airflow Performance

    1070 1020 1030 PCE6A36 Low cool 1360 1330 1290 1250 1210 1160 1110 1060 1020 1260 1220 1180 1140 1100 1050 Heat 1150 1110 1070 1020 1030 See notes at end of table on next page. Johnson Controls Ducted Systems...
  • Page 12: Electric Heat Performance Data

    18.0 22.0 1. (0,1): 0 = no service disconnect or 1 = with service disconnect. 2. (1,2): 1 = with service disconnect, no breaker jumper bar or 2 = with service disconnect and breaker jumper bar. Johnson Controls Ducted Systems...
  • Page 13: Section Vi: Operation

    HEAT speed based on the HEAT jumper setting. When the thermostat ends the call for FAN, the thermostat terminal G is de-energized, and the indoor blower control board stops the indoor cir- culating blower operation. Johnson Controls Ducted Systems...
  • Page 14: Delay Profile Descriptions

    PCE6A36 D (LO) C (ML) C (ML) A (HI) — — PCE6B48 D (LO) D (LO) D (LO) C (ML) B (MH) — PCE6B60 D (LO) D (LO) C (ML) D (LO) B (MH) A (HI) Johnson Controls Ducted Systems...
  • Page 15: Indoor Blower Control

    5. Compare the readings taken to the unit charging chart. speed is set at or above the required speed. See Table 17. 8. Make sure that all the unit panels are in place and secured, and that an air filter is installed. Johnson Controls Ducted Systems...
  • Page 16: Measuring External Static Pressure

    Clean as often as necessary to keep the coil clean. If using water to clean the coil, make sure that the power to the unit is shut off before cleaning. NOTICE Do not use a pressure washer as coil fin damage will occur. Johnson Controls Ducted Systems...
  • Page 17: Section Viii: Typical Wiring Diagrams

    6310638-UIM-B-0823 Section VIII: Typical wiring diagrams Figure 11: Connection wiring diagram Johnson Controls Ducted Systems...
  • Page 18: Ladder Wiring Diagram

    6310638-UIM-B-0823 Figure 12: Ladder wiring diagram Johnson Controls Ducted Systems...
  • Page 19: R-410A Quick Reference Guide

    If system must be opened for service, evacuate system then break the vacuum with dry nitrogen and replace all filter driers. Figure 13: R-410A quick reference guide Third-Party Trademarks: For information about third-party trademarks, refer to the relevant company websites. Johnson Controls Ducted Systems...
  • Page 20 6310638-UIM-B-0823 NOTES Johnson Controls Ducted Systems...
  • Page 21: Section Ix: Start-Up Sheet

    Outside air dry bulb temperature Return static (inches of water column) Return air dry bulb temperature Return air wet bulb temperature Total external static pressure Temperature drop Supply air wet bulb temperature Page 1 of 2 (10/29/12) Johnson Controls Ducted Systems...
  • Page 22 Explain the importance of regular filter replacement and equipment maintenance Comments and Additional Job Details Page 2 of 2 (10/29/12) Subject to change without notice. Published in U.S.A. 6310638-UIM-B-0823 Copyright © 2023 by Johnson Controls. All rights reserved. Supersedes: 6310638-UIM-A-1222 York International Corp. 5005 York Drive Norman, OK 73069...

This manual is also suitable for:

Pce6a24Pce6a36Pce6b48Pce6b60

Table of Contents