Johnson Controls PCE4 Series Installation Manual
Johnson Controls PCE4 Series Installation Manual

Johnson Controls PCE4 Series Installation Manual

Single package air conditioner/electric heat
Hide thumbs Also See for PCE4 Series:

Advertisement

Quick Links

INSTALLATION MANUAL
Single Package
Air Conditioner/Electric Heat
Models: PCE4 Series
2 ton to 5 ton - 208/230 V - Single-Phase
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Model number nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Airflow performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Component location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Unit 4-point load weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Bottom duct dimensions (in.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rear duct dimensions (in.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit limitations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Application limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Weights and dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Section I: General information

PCE units are factory-assembled air conditioners designed for outdoor
installation on a rooftop or a slab. Field-installed electric heater acces-
sories are available to provide electric heat.
The units are completely assembled on rigid, removable base rails. All
piping, refrigerant charge, and electrical wiring is factory installed and
tested. The units require only electric power and duct connections at
the point of installation.

Section II: Safety

This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
Johnson Controls Ducted Systems
List of sections
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Typical wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Start-up sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
List of figures
Typical field power wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Single-point wiring kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Measuring external static pressure . . . . . . . . . . . . . . . . . . . . . . . . . 15
R-410A quick reference guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Connection wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Ladder wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
List of tables
Electric heat performance data: 208/230-1-60 . . . . . . . . . . . . . . . . 10
Single-point wiring kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Physical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Airflow performance - side duct application . . . . . . . . . . . . . . . . . . . 12
Electric heat minimum supply air . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Electric heat multipliers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Additional static resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Thermostat signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service, or maintenance
can cause injury or property damage. Failure to carefully read and
follow all instructions in this manual can result in furnace mal-
function, death, personal injury, and/or property damage. Only a
qualified contractor, installer, or service agency should install this
product.
This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
Assembled at a facility with
an ISO 9001:2015-certified
®
Quality Management
WARNING
!
CAUTION
!
6310634-UIM-B-0623
System

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PCE4 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Johnson Controls PCE4 Series

  • Page 1: Table Of Contents

    INSTALLATION MANUAL Single Package Air Conditioner/Electric Heat Assembled at a facility with an ISO 9001:2015-certified Models: PCE4 Series ® Quality Management System 2 ton to 5 ton - 208/230 V - Single-Phase List of sections General information ........1 Operation .
  • Page 2: Section Iii: Model Number Nomenclature

    Air Conditioning Contractors of America codes (Manual J). Table 1: Unit limitations Unit limitations Model Unit voltage Applied voltage Outdoor DB temperature (°F) Minimum Maximum Maximum PCE4A24 208/230-1-60 PCE4A30 208/230-1-60 PCE4A36 208/230-1-60 PCE4A42 208/230-1-60 PCE4B48 208/230-1-60 PCE4B60 208/230-1-60 Johnson Controls Ducted Systems...
  • Page 3: Rigging And Handling

    Before lifting, make sure the unit weight is distributed equally on the rigging cables so it will lift evenly. Units can be moved or lifted with a forklift. Slotted openings in the base rails are provided for this purpose. Johnson Controls Ducted Systems...
  • Page 4: Unit 4-Point Load Weight

    COIL GUARD HIGH VOLTAGE OPENING 7/8” HIGH VOLTAGE OPENING 1-3/32” HEAT SECTION COMPRESSOR ACCESS PANEL ACCESS PANEL CONDENSATE DRAIN BLOWER LOW VOLTAGE OPENING 7/8” ACCESS CONTROL / HEAT PANEL ACCESS PANEL A0379-003 Figure 3: Unit dimensions Johnson Controls Ducted Systems...
  • Page 5: Bottom Duct Dimensions (In.)

    24, 30, 36, 42 or install a filter/frame kit. 48, 60 13.6 A filter rack and high velocity filters are standard on three-phase units. Figure 5: Rear duct dimensions (in.) Johnson Controls Ducted Systems...
  • Page 6: Typical Field Control Wiring Diagram For Air Conditioner Models

    NEC/CEC. Voltage tolerances that must be main- tained at the compressor terminals during starting and running condi- tions are indicated on the unit Rating Plate and Table 1. Note: Provide the wiring entering the cabinet with mechanical strain relief. Johnson Controls Ducted Systems...
  • Page 7: Electrical Data For 208/230-1-60 Single Source Power

    73.8 80.6 6HK16502006 14.4 17.6 69.3 76.7 95.4 104.6 1. Minimum circuit ampacity 2. Maximum overcurrent protection per standard UL 1995 3. Fuse or HACR circuit breaker is field installed 4. Single-point connection kit is required Johnson Controls Ducted Systems...
  • Page 8: Electrical Data For 208-1-60 Multi Source Power - Pce4

    52.0 36.5 65.0 6HK26502006 14.4 69.3 36.5 86.7 6HK26502506 18.0 86.7 36.5 108.3 1. MCA = Minimum circuit ampacity 2. MOP = Maximum overcurrent protection device. Must be HACR type circuit breaker or time delay fuse Johnson Controls Ducted Systems...
  • Page 9: Electrical Data For 230-1-60 Multi Source Power - Pce4

    80.0 6HK26502006 17.6 76.7 36.5 95.8 100.0 6HK26502506 22.0 95.8 36.5 119.8 125.0 1. MCA = minimum circuit ampacity 2. MOP = Maximum overcurrent protection device. Must be HACR type circuit breaker or time delay fuse Johnson Controls Ducted Systems...
  • Page 10: Single-Point Wiring Kits

    Up to 15 kW PCE4A36 S1-2SPWK002 35 A Up to 15 kW PCE4A42 S1-2SPWK007 40 A Up to 20 kW PCE4B48 S1-2SPWK003 45 A Up to 20 kW PCE4B60 S1-2SPWK004 50 A Up to 20 kW Johnson Controls Ducted Systems...
  • Page 11: Physical Data

    For internal filter use, a filter rack kit is available. Refer to the instructions supplied with the kit for replacement filter sizes. Filter sizes: A = 20 in. x 20 in., B = 20 in. x 30 in. Johnson Controls Ducted Systems...
  • Page 12: Section V: Airflow Performance

    Minimal variations in airflow performance data result from operating at 208 V. The data in the table can be used in those cases. Heating applications are tested at 0.50 in. W.C. external static pressure. Cooling applications are tested per AHRI Standard 210/240. The differences between side duct airflows and bottom duct airflows are insignificant. Johnson Controls Ducted Systems...
  • Page 13: Electric Heat Minimum Supply Air

    Table 14: Electric heat multipliers Voltage kW capacity multipliers Nominal Applied 0.75 0.92 1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat capacity for heaters applied at lower voltages. Johnson Controls Ducted Systems...
  • Page 14: Thermostat Signals

    CFM during full economizer operation. 4. Obtain an entering indoor wet bulb temperature reading. Note: Filter pressure drop based on standard filter media tested at velocities not to exceed 300 ft/min. 5. Compare readings taken to the unit charging chart. Johnson Controls Ducted Systems...
  • Page 15: Section Vii: Maintenance

    If using water to clean the coil, ensure that the power to the CAUTION unit is shut off before cleaning. The wire number or color and terminal designations referred to may vary. Check the wiring label inside the control box access panel for the correct wiring. Johnson Controls Ducted Systems...
  • Page 16: R-410A Quick Reference Guide

    If system must be opened for service, evacuate system then break the vacuum with dry nitrogen and replace all filter driers. Figure 10: R-410A quick reference guide Third-Party Trademarks Notice: For information about third-party trademarks, refer to the relevant company websites. Johnson Controls Ducted Systems...
  • Page 17: Section Viii: Typical Wiring Diagrams

    FOR IDENTIFICATION. VERIFY PROPER OPERATION AFTER SERVICING. 3. FACTORY WIRED FOR 230 VOLT SUPPLY POWER. FOR 208 VOLT, MOVE BLACK WIRES FROM THE 230 TO THE 208 VOLT TAP ON THE TRANSFORMER. Figure 11: Connection wiring diagram Johnson Controls Ducted Systems...
  • Page 18: Ladder Wiring Diagram

    FOR PROPER SPEED TAP INFORMATION FOR EACH APPLICATION TO OBTAIN 3A FUSE 40 VA APPROX. 400 CFM/TON IN COOLING. THERMOSTAT HI PRESSURE WIRING DIAGRAM FOR SWITCH HEATER KITS: 6HK*6501306 6HK*6501506 CONTACTOR COIL BLOWER EQUIPMENT MOTOR GROUND SEQ2 SEQ1 RED/WHT Figure 12: Ladder wiring diagram Johnson Controls Ducted Systems...
  • Page 19: Section Ix: Start-Up Sheet

    Outside air dry bulb temperature Return static (inches of water column) Return air dry bulb temperature Return air wet bulb temperature Total external static pressure Temperature drop Supply air wet bulb temperature Page 1 of 2 Johnson Controls Ducted Systems...
  • Page 20 Explain the importance of regular filter replacement and equipment maintenance Comments and Additional Job Details Subject to change without notice. Published in U.S.A. 6310634-UIM-B-0623 Copyright © 2023 by Johnson Controls. All rights reserved. Supersedes: 6310634-UIM-A-1122 York International Corp. 5005 York Drive...