Checking Duct Static; Checking Temperature Rise - Amana GMES9 Series Service And Troubleshooting

Single stage gas furnaces and accessories
Table of Contents

Advertisement

SERVICING
COOL MOTOR SPEED DIP SWITCH SETTING (S1-1, S1-2, S1-3)
1
2
Position OFF OFF OFF ON OFF OFF ON ON OFF OFF ON OFF
Motor
Y
T1
Speed
COOL
*1
2
Position OFF OFF ON OFF ON ON ON OFF ON ON ON ON
Motor
Y
T1+T2
Speed
COOL
* = DEFAULT SETTING
HEAT MOTOR SPEED DIP SWITCH SETTING (S2-1, S2-2)
1
Position OFF OFF ON OFF ON ON OFF ON
Motor
W
T1
Speed
HEAT
* = DEFAULT SETTING
FAN MOTOR SPEED DIP SWITCH SETTING (S2-3, S2-4)
*3
Position OFF OFF ON OFF OFF ON ON ON
Motor
G
T1
Speed
FAN
* = DEFAULT SETTING
S-200

CHECKING DUCT STATIC

The maximum and minimum allowable external static
pressures are found in the specification section. These tables
also show the amount of air being delivered at a given static
by a given motor speed or pulley adjustment.
The furnace motor cannot deliver proper air quantities (CFM)
against statics other than those listed.
Too great of an external static pressure will result in insufficient
air that can cause excessive temperature rise, resulting in
limit tripping, etc. Whereas not enough static may result in
motor overloading.
To determine proper air movement, proceed as follows:
1. With clean filters in the furnace, use a draft gauge (inclined
manometer) to measure the static pressure of the return
duct at the inlet of the furnace. (Negative Pressure)
2. Measure the static pressure of the supply duct. (Positive
Pressure)
3. Add the two (2) readings together for total external static
pressure.
NOTE: Both readings may be taken simultaneously and read
directly on the manometer if so desired. If an air conditioner
coil or Electronic Air Cleaner is used in conjunction with the
furnace, the readings must also include theses components,
as shown in the following drawing.
4. Consult proper tables for the quantity of air.
If the total external static pressure exceeds the minimum
or maximum allowable statics, check for closed dampers,
registers, undersized and/or oversized poorly laid out duct
work.
3
1
2
3
1
2
3
T2
T3
3
1
2
3
1
2
3
T1
T1
2
*1
2
1
2
T2
T3
4
3
4
3
4
T2
T4 T1+T2
1
2
3
T4
1
2
3
T1
1
2
T4
3
4
S-201

CHECKING TEMPERATURE RISE

The more air (CFM) being delivered through a given furnace,
the less the rise will be; so the less air (CFM) being
delivered, the greater the rise. The temperature rise should
be adjusted in accordance to a given furnace specifications
and its external static pressure. An incorrect temperature
rise may result in condensing in or overheating of the heat
exchanger. An airflow and temperature rise table is provided
in the blower performance specification section. Determine
and adjust temperature rise as follows:
1. Operate furnace with burners firing for approximately ten
minutes. Check BTU input to furnace - do not exceed
input rating stamped on rating plate. Ensure all registers
are open and all duct dampers are in their final (fully or
partially open) position.
2. Place thermometers in the return and supply ducts as
close to the furnace as possible. Thermometers must not
be influenced by radiant heat by being able to "see" the
heat exchanger.
Checking Static Pressure
SUPPLY
RETURN
AIR
Checking Temperature Rise
AIR
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents