Fireye BurnerPRO BP110 Manual page 31

Microprocessor-based integrated burner management control
Hide thumbs Also See for BurnerPRO BP110:
Table of Contents

Advertisement

NO
FAULT
37
INPUTS WAITING TIME FAULT
38
SUPV SW WDT RESET
39
SUPV SW RESET
40
HARDWARE RESET
41
SUPV HARDWARE RESET
42
MAIN LOOP STUCK FAULT
43
SUPV LOOP STUCK FAULT
44
SUPV TIMER2 FAULT
45
MAIN AC PEAK MISSING FAULT
46
SUPV AC PEAK MISSING FAULT
47
UV PULSE INPUT MISSMATCH
48
SUPERVISORY MCU ADC FAULT
49
MAIN MCU ADC FAULT
50
IGNITION FEEDBACK FAULT
51
PILOT_FEEDBACK_FAULT
52
MAINP_FEEDBACK_FAULT
53
FEEDBACK_WAITING_TIME_EXPIRE
54
MAIND_FEEDBACK_FAULT
55
INTERRUPT DIAG FAULT
56
FALSE_FLAME_ERROR
57
POWERON_FALSE_FLAME_ERROR
58
OPEN_FEEDBACK_READING_FAULT
59
ADJACENT PIN SHORT FAULT
60
LOCAL RESET DEBOUNCE FAULT
61
POC OPEN FAULT
62
STRONG UV FLAME FAULT
63
SPI CRC FAULT
System was unable to satisfy combustion air switch test and/or proof of closure during a burner sequence. Check wiring.
Check air-flow switch.
Internal software reset by Microcontroller. Contact distributor/factory if error persists.
Internal software reset by Microcontroller. Contact distributor/factory if error persists.
Replace control. Contact distributor/factory if error persists.
Replace control. Contact distributor/factory if error persists.
Replace control. Contact distributor/factory.
Replace control. Contact distributor/factory.
Replace control. Contact distributor/factory.
Check Mains voltage. Contact distributor/factory.
Check Mains voltage. Contact distributor/factory.
Replace control. Contact distributor/factory.
Replace control. Contact distributor/factory.
Replace control. Contact distributor/factory.
System detected voltage on terminal 16 at the wrong time or voltage is not present when needed. Check wiring and make
sure grounding is adequate.
System detected voltage on terminal 17 at the wrong time or voltage is not present when needed. Check wiring and make
sure grounding is adequate.
System detected voltage on terminal 19 at the wrong time or voltage is not present when needed. Check wiring and make
sure grounding is adequate.
Loss of actuator feedback for more than 10 minutes. Check wiring. Check modulation equipment.
System detected voltage on terminal 18 at the wrong time or voltage is not present when needed. Check wiring and make
sure grounding is adequate.
Replace control. Contact distributor/factory.
False flame detected before Ignition. Check wiring. Check scanner. Make sure grounding is adequate.
False flame detected at power on. Check wiring. Check scanner. Make sure grounding is adequate.
System detected voltage on terminal 8 at the wrong time or voltage is not present when needed. Check wiring and make
sure grounding is adequate.
Replace control. Contact distributor/factory.
Local reset button held for more than 10 seconds or reset button is stuck.
Fuel valve is open at the wrong time OR check wiring
Scanner too close to flame. Add distance between scanner and flame OR use orifice to reduce field of view.
Replace control. Contact distributor/factory
POSSIBLE REMEDY
®