PF3100 TROUBLESHOOTING – SOLUTIONS TO COMMON PROBLEMS
Main flame fail
The main flame ion failed to detect flame after the main valves opened.
Solution:
Check that the main flame detect rod is positioned in the flame. Test the ion input DC and AC voltage levels.
Confirm main gas is flowing.
Level or pressure contact range error
The input to the level or pressure input is out of bounds from what is expected. The signal may be too low (in the
case of 4-20mA input) or too high.
Solution:
In the case of the 4-20mA signal check the current and confirm it is within range (4 to 20mA). If used as a digital
input, check that the voltage does not exceed the input range of 12 or 24VDC depending on the system power
supply.
Feature Key Alarm
The feature key is not present or is the incorrect one for the system.
Solution:
You can confirm the feature key details in settings > Setup > Feature Key menu. Here a feature key status is
available that shows if the key is currently detected, is invalid or has a fault. A list of system restrictions is shown
for items such as pilot per controller, IO per appliance and number of controllers per appliance. If any of these
items are violated a feature key alarm will be set.
Low or High voltage warning
If low the system voltage is below it's desired operating range. If the voltage continues any lower the system will
shutdown. If high the system voltage is above its desired operating range. If the voltage continues any higher the
system will shutdown.
Solution:
Confirm the voltage settings match the power supplied to the system by going to Settings > Setup > System
Voltage. The Controller voltage should match the input power of the system. Check with a multi-meter that the
power supplied to the system is correct – either 12 or 24VDC. If the voltage drops when the valves turn on
confirm the power supply is sized appropriately for the current load.