PF3100 TROUBLESHOOTING – SOLUTIONS TO COMMON PROBLEMS

4.1.2 Wiring lengths

Wire
Ignition coil control
wires
High voltage ignition
PFRN

4.1.3 LED Indication

LED
Link
Power
LEL Fault
Coil Fault
Main Fault
Pilot Fault
Description
It is suggested to keep the ignition coil in the enclosure and the wires to it (red, white
and black) as short as possible.
The ignition wire should be 10 feet or less from the coil.
Up to 250 feet.
Indication
Solid green when there is a link or off without a link.
If the link LED is not solid green check the PFRN wiring.
Solid blue when the port is powered or off if not powered.
If the power LED is not solid blue check the PFRN wiring and the host card power (switch
or BMS depending on the install).
6. Internal LEL input circuit fault.
7. LEL out of range alarm.
8. Calibration error
9. Calibration error
10. Main flame detection internal circuit fault.
11. Internal calibration error
12. Main Ion+ wiring error including a grounded probe.
13. Pilot flame detection internal circuit fault.
14. Internal calibration error.
15. Pilot Ion + wiring error. A grounded probe may not trigger this fault due to the
internal resistance of the ignition coil.
©2016 Profire Energy Inc. – All rights reserved. No part of this publication
may be reproduced, distributed, or transmitted in any form without the prior
written permission of the publisher for reasons other than personal use
V1.1
Nov 29, 2016
Page 13